Содержание MT-101

Страница 1: ......

Страница 2: ...MT 101 Telemetry Module MT 101 User s Manual GSM GPRS Telemetry Module for monitoring and control Class 1 Telecommunications Terminal Equipment for GSM 850 900 1800 1900 v1 43 INVENTIA Sp z o o ...

Страница 3: ...ntia pl http www inventia pl Copyright 2002 2008 INVENTIA Sp z o o All rights reserved Version 1 43 Warsaw April 2008 Please note This User s Manual is related to the version 1 43 of the firmware software of the MT 101 Telemetry Module Versions older than the one described in the Manual may not support all the features ...

Страница 4: ...9 Housing 17 5 Connections scheme 17 5 1 Binary inputs I1 I8 17 5 2 Binary inputs outputs Q1 Q8 18 5 3 Analog inputs A1 A2 19 5 4 Communication ports 20 5 5 Power supply 22 6 Starting the module 23 6 1 Connecting antenna 23 6 2 First configuration 24 6 3 Inserting SIM card 25 6 4 Start up 25 7 Module s operating modes 26 7 1 MT Slave mode 27 7 2 Transparent mode 27 7 3 Modbus RTU Master mode 27 7 ...

Страница 5: ... Device IP 40 8 2 3 5 IP assignment 40 8 2 3 6 Set IP 41 8 2 3 7 Virtual IP address 41 8 2 3 8 Number of GPRS transmission retries 41 8 2 3 9 Transmission timeout 42 8 2 3 10 Idle time 42 8 2 3 11 GPRS testing IP address 42 8 2 3 12 Number of login retries 43 8 2 3 13 Wait time after disconnection 43 8 2 3 14 Data frame format 43 8 2 3 15 Proxy server IP address 44 8 2 3 16 CRC compatibility 44 8 ...

Страница 6: ...s 55 8 2 5 6 6 Number of devices 55 8 2 5 6 7 MC 1 16 55 8 2 5 6 7 1 Address 55 8 2 5 6 7 2 Alarm reading 55 8 2 5 6 7 3 Signal reading 56 8 2 5 6 7 4 Current data reading 56 8 2 5 6 7 5 Current data block index 56 8 2 5 6 7 6 Current data block length 56 8 2 5 7 M Bus LEC mode 57 8 2 5 7 1 Read interval 57 8 2 5 7 2 Number of retries 57 8 2 5 7 3 Transmission timeout 57 8 2 5 7 4 Threshold hyster...

Страница 7: ... 2 2 Low reference internal units 67 8 2 6 2 2 2 2 3 Low reference engineering units 67 8 2 6 2 2 2 2 4 High reference internal units 68 8 2 6 2 2 2 2 5 High reference engineering units 68 8 2 6 2 2 2 2 6 Alarm HiHi 68 8 2 6 2 2 2 2 7 Alarm Hi 68 8 2 6 2 2 2 2 8 Alarm Lo 68 8 2 6 2 2 2 2 9 Alarm LoLo 69 8 2 6 2 2 2 2 10 Alarm hysteresis 69 8 2 6 2 2 2 2 11 Dead band 69 8 2 6 2 2 2 3 Counter inputs...

Страница 8: ...of SMS sending rules 79 8 2 7 1 2 SMS sending rule 79 8 2 7 1 2 1 Trigger input 79 8 2 7 1 2 2 Trigger flag 79 8 2 7 1 2 3 SMS text 80 8 2 7 1 2 4 Recipient number 80 8 2 7 1 2 5 Status sending 80 8 2 7 2 Data sending 81 8 2 7 2 1 Number of data sending rules 81 8 2 7 2 1 1 Data sending rule 81 8 2 7 2 1 1 1 Trigger input 81 8 2 7 2 1 1 2 Trigger flag 82 8 2 7 2 1 1 3 IP address 82 8 2 7 2 1 1 4 S...

Страница 9: ...e in the registry 112 9 14 7 Alarm with confirmation 113 9 14 8 Motion detector 114 9 14 9 Logger program 114 10 Problem solving 115 10 1 LED signaling 115 10 1 1 Inputs Outputs Q1 Q8 116 10 1 2 Inputs I1 I8 116 10 1 3 GSM status 117 10 1 4 GSM activity 117 10 1 5 GSM signal level 118 10 1 6 PORT 2 activity 118 10 1 7 Module s status 119 10 1 8 SET1 SET2 alarm thresholds 120 10 2 Unblocking of SIM...

Страница 10: ...parent mode 133 13 2 2 2 2 Configuration for GazModem mode 133 13 2 2 2 3 Configuration for M Bus Lec mode 134 13 2 2 2 4 Configuration for NMEA 0183 mode 134 13 3 Syntax for reading and writing data in SMS mode 135 13 4 Unlocking writing to internal registers 136 13 5 Working with dynamic IP addressing 136 13 6 Data formats 137 13 7 Module s Status format 138 13 8 Trigger inputs 138 13 9 Flags 13...

Страница 11: ...nection time rather than the amount of the transferred data In this situation the real time monitoring of units requiring constant supervision but generating a relatively small amount of data was not possible The situation changed radically after GSM operators introduced data transmission services in the GPRS General Packet Radio Services standard The new technology called the 2 5G standard meanin...

Страница 12: ...inted with the modules configuration and modes of operation along with examples of application in different configurations described in appendices 3 GSM requirements For proper operation the module needs a SIM card supplied by a GSM operator providing GPRS and or SMS services The GPRS enabled SIM card has to be registered in the APN with static IP addressing The unique IP address of the SIM card i...

Страница 13: ...nary outputs 8 working as binary otput binary input counter input analogue input F U C counters 0 max 16 each input and output can work as a counter input AI analogue inputs 2 16 4 20 mA as analogue F U created of binary inputs and outputs Serial PORT 1 1 standard RS232 for configuration only Serial PORT 2 1 standard RS232 422 485 different communication protocols ...

Страница 14: ... signal frequency to analog conversion so for proper operation one has to connect analog signal source via analog to frequency converter which outputs a square wave of frequency proportional to analog signal Input signal conversion range is 0 2kHz During configuration of analogue inputs the user can set engineering units and precisely rescale the input signal The alarm levels and the time of input...

Страница 15: ...ication with external data sources The interface and operating mode is selected during module s configuration This port is optoisolated 4 2 5 Real time clock MT 101 Module is equipped with astronomical time clock RTC The clock is a base for defining working cycles of module timers and time stamps for measurement results recorded in registers Imprecise clock setting results in faulty time stamping ...

Страница 16: ...o 24 h with synchronization with module z RTC clock Properly configured clock counts the time setting after each completed period for one program cycle a flag in binary inputs space respective TMR1 TMR2 TMR3 TMR4 These flags can be used in internal controlling program or for triggering transmission on event 4 3 4 Counters Each of MT 101 module s inputs outputs is capable of counting pulses and sto...

Страница 17: ... bits are set for 1 program cycle immediately after reception and recording it in MT2MT buffer 4 Data transmission in this system copies registers of sending module into the exact same register in receiving module When designing communication between larger number of modules separate register areas have to be sent and appropriately large areas define for MT2MT receiving buffer in receiving modules...

Страница 18: ...ual setting of auxiliary alarm thresholds for analogue inputs A1 and A2 Manually set thresholds can not be modified or read during configuration of module There are two flags connected to these thresholds ANX_Set_F and ANX_Set_R informing about crossing of the set level and two alarms An Set Fall and An Set Rise that may be used for rule processing ...

Страница 19: ...bsence of static IP address use of the module for GPRS transmission is impaired Proper placement of the SIM card is imperative for module s operation The module accepts only SIM cards operating in low potential technology 3 3V 4 7 Antenna Attachment of antenna is essential for proper operation of MT 101 telemetry module SMA socket is placed on module s front panel The attached antenna has to secur...

Страница 20: ...ag may be used for rules processing The input may be used to signal main supply failure and switch over to battery supply 4 9 Housing MT 101 module is encapsulated in standard housing made of plastic compliant with safety requirements and protecting the module in standard operating environment The applied solution complies with standard industrial requirements for DIN rail mounting 5 Connections s...

Страница 21: ...put and storing the result in a 32 bit register assigned to this input Binary input operating in analogue mode has slightly different connection It is assumed that the signal is a square wave with variable frequency in range 0 2kHz where momentary frequency corresponds to measured analogue value The wave usually comes from a converter exchanging measured analogue value to proportional frequency in...

Страница 22: ...t and storing the result in a 32 bit register assigned to this input Binary input operating in analogue mode has a slightly different connection It is assumed that the signal is a square wave with variable frequency in range 0 2kHz where momentary frequency corresponds to measured analogue value The wave comes usually from a converter that exchanges measured analogue value to proportional frequenc...

Страница 23: ...rts Telemetry module is equipped with 2 communication ports for different applications They are PORT 1 RS232 configuration The not optically isolated Port is used for configuration Connection point to point to PC via RS 232 DB 9 connector female Pin description 1 2 TXD transmitter output 3 RXD receiver input 4 5 GND ground 6 7 CTS handshake input 8 RTS handshake output 9 ...

Страница 24: ...iption TXD transmitter output RXD receiver input COM interface common ground GND RT terminator if necessary connect to RD RD RD for RS485 transmitter receiver for RS422 receiver SD SD for RS422 transmitter For RS232 mode the length of the cable should not exceed 15 m NOTICE Supply cables length 10 m Signal cables length 30 m For longer cables it is recommended to use external overvoltage protectio...

Страница 25: ...t employed shortcut with Positive pole of power supply Negative pole of power supply Not recommended in standard appliances since it may increase emitted noise For AC supply polarisation does not apply Example Connection diagram with battery backup NOTICE Due to MT 101 module s high momentary current consumption the supply must be capable of delivering 2A current Improper power supply may result i...

Страница 26: ...ration The type of antenna depends on the desired mounting type and power of GSM signal in antenna placement area As previously mentioned the antenna has to be attached at every power up because it is a necessary transmitter load and absence endangers the module s transmitter part Even with no SIM inserted the module exchanges information with available GSM networks in order to secure possibility ...

Страница 27: ...TM User Manual Logging into GSM GPRS network requires basic information about the SIM card in use and optionally about the APN that the module is going to operate within when GPRS mode is turned on The parameters are In General group PIN code for SIM card insert PIN code of the SIM card intended for the module unless the card is configured not to ask for PIN code Use GPRS Yes if SMS and GPRS packe...

Страница 28: ...wrong PIN code resultingn permanent locking of access to SIM card and subsequent permanent locking of module Should this happen the SIM card has to be unlocked using the PUK code The details of the procedure unlock the card is described in chapter Problem solving Insert SIM card in cradle and slide it into the slot as depicted below until the gentle click is heard Properly inserted SIM cards secur...

Страница 29: ...ing it as a plain but automatically logging into selected network GSM GPRS modem Modbus RTU Mirror Mode adds to Modbus RTU Slave mode a very sophisticated functionality enabling using the module as local Master of Modbus RTU protocol The module is mapping registers of external Modbus devices into it s own internal registers This functionality significantly reduces GPRS transmission necessary for e...

Страница 30: ... of the response the module reserves for a defined time the direct communication channel with the module that responded to the last query thus creating a temporary point to point connection The reservation time is counted since reception of last GPRS packet Consecutive packets received from that module prolong channel reservation while sending packets does not prolong the reservation When channel ...

Страница 31: ...rces of the system If Modbus ID of received frame does not match module s ID the frame is forwarded to PORT2 and may be received by the Master device 7 4 Modbus RTU Slave mode In this mode the module acts as a network node serving both own resources and all connected to PORT2 devices operating in Modbus RTU Slave mode waiting for GPRS data frames Upon reception of the frame it investigates recipie...

Страница 32: ... resources as well as resources of any slave connected to PORT2 The addition feature provides the possibility of resource mapping of devices connected to PORT2 into internal module Registers With this option active the module cyclically reads mapped areas of external devices and refreshes internal Registers Writing to external devices is possible as well In Mirror mode for every internal program c...

Страница 33: ...mber of addresses defined in GPRS section The function of channel reservation is independent of access frames Reception of access frame does not reserve the channel Access to the module from another master during channel reservation is possible Bear in mind that In this mode the module may exchange GPRS data correctly with modules operating in Modbus Master mode Modbus Slave Modbus Mirror if the C...

Страница 34: ...e High order byte remains unused Data reception Configuration for FlexSerial mode uses 2 variables that define the way data stream received at PORT 2 is converted into data packets available for internal program Received data is stored in registers Registers P2RCV_B1 P2RCV_B512 build the receiving buffer Register P2RCV_NO controls data reception Data received at PORT 2 is internally buffered in 6k...

Страница 35: ...l information The configuration of MT 101 module as is the case for other modules in the MT series is carried out using the MTM MT Manager program portal delivered free of charge to users of our telemetry solutions The portal is a specialized environment providing full control of the entire telemetry system regardless of the system s size The possibility of dividing hardware resources into Project...

Страница 36: ...n contained by module and configuration file version Information displayed is not user editable and solely used for verification and information purpose 8 2 1 1 Module name Function displays name assigned to module during configuration Data type text Range n a read only parameter Comments n a 8 2 1 2 Module type Function displays the type of configured telemetry module Data type text Range n a rea...

Страница 37: ...cally by 1 after each successfully stored configuration 8 2 1 8 Last configuration date Function displays time and date of last successful configuration change Data type text Range n a read only parameter Comments the value changes automatically with successful configuration change Useful in tracing unauthorized configuration changes 8 2 1 9 Last read of device time Function displays internal modu...

Страница 38: ...ts Modbus ID are serviced locally while frames carrying other Modbus IDs are sent to PORT2 Modem in this mode the module acts as GPRS modem controlled by AT commands At power on the module uses PIN code defined during configuration and logs on to GSM network Modbus RTU Mirror mode enables remote querying of module resources along with attached units working in Modbus RTU protocol and event trigger...

Страница 39: ...pe text Range letters and numerals max 8 characters Default value 0000 Comments wrong pin can cause locking of SIM module CAUTION Caution is vital when setting the PIN code value Entering faulty PIN code may cause module start up to be impossible and lock SIM card In latest versions of the module attempting to enter wrong PIN code twice renders a third attempt impossible 8 2 2 3 GSM band Function ...

Страница 40: ...ts since the only way of unlocking the module is resetting it to factory settings it is vital that the password is stored in a safe way and available when needed 8 2 2 6 Configuration reading block Function blocks reading of module configuration even when using valid password Data type selection list Range Yes Reading of configuration from the module is impossible No Module is not protected agains...

Страница 41: ...iting to module is possible only after providing valid password The procedure to be followed in this case is to be found in chapter Appendices Unblocking writing to internal registers 8 2 2 10 Error display time Function Defines in seconds error display time on Status GSM and SGN LEVEL and on ERR LED groups Data type number Range 1 60 s Default value 30 s Comments setting of too small value makes ...

Страница 42: ...led number of sent messages thus saving on running expenses Setting the parameter to 0 removes the limit Data type number Range 0 65 535 Default value 0 Comments This parameter is available in no GPRS and in GPRS mode with Yes option for use SMS chosen CAUTION Reaching the limit set by this parameter results in unconditional without warning stop of SMS sending Note that no SMS will be sent until t...

Страница 43: ...uired by GSM network operator 8 2 3 3 APN password Function defines password for APN user account Data type text Range letters numerals special characters max 32 characters Default value empty Comments Optional parameter used only if required by GSM network operator 8 2 3 4 Device IP Function allows user to define IP number for newly created module definition and displays IP number read from the m...

Страница 44: ...e in GSM networks where operator uses dynamic address translation of internal addresses to static external addresses visible to external users The parameter enables placing the external IP address under which the internal network node is visible in the header for sent data frame As a result external recipients will experience match of sender s IP with IP address written in data header It is necess...

Страница 45: ...ctivity longer than the value defined in this parameter the module sends a control frame in order to check whether transmission is still possible During network check control data frame is sent to module s own IP address respecting timeout and number of retries parameters The length of the frame is 45B length of the module s name The frame is sent to module s own IP address or to the address defin...

Страница 46: ...me after disconnection Function Defines interval in seconds before resuming after failed login attempt Data type number Range 0 60 s Default value 5 s Comments Setting the value to 0 results in immediate retries 8 2 3 14 Data frame format Function This parameter selects data frame type used by module for GPRS communication and indirectly the operating mode Data type selection list Range Standard S...

Страница 47: ...ures compatibility with MT DP communication software No for maintaining compatibility when expanding existent systems operating in MODBUS modes or cooperating with old versions of OPC driver Default value Yes Comments in new systems it is recommended to leave the option at default value Yes 8 2 4 Authorized numbers This group holds lists of telephone numbers and IP addresses authorized to communic...

Страница 48: ...e list may be edited using context menu activated by right mouse click Available operations depend on the cursor placement When cursor rests on an entry all options are available while only Append is available with cursor resting on active window s background 8 2 4 4 IP Idx list index number Name friendly name of the IP number facilitating identification in Rules processing Max length 16 character...

Страница 49: ...n transparent mode the module receiving data at serial port buffers it in internal memory and converts it to data packet to be sent to defined recipients During packets creation criteria described by variables of GPRS transmission sub group are applied Additionally parameters allowing packet routing in order to reduce transmitted data volume are defined Packet routing is possible only when the pla...

Страница 50: ...icantly Packets are sent to all recipients only at first transmission The function is activated by setting the value other to than zero thus defining the time channel is reserved Time count starts from receiving first GPRS packet Consecutive packets from same source prolong reservation time while sent packets do not Setting this variable to 0 switches reservation off and module operates in standar...

Страница 51: ... length of data packet and Data packet delimiter so that all data frames will be received completely 8 2 5 1 1 6 Broadcast address Function Defines recipient address If detected in address field of the frame received at PORT 2 will cause sending of this frame to all recipients defined in routing table Data type number Range 0 65535 Default value 0 Comments Placing this address in routing table wil...

Страница 52: ...number Range 1 255 Default value 1 Comments the length of routing table should not be shorter than number of network nodes the module communicates with 8 2 5 2 2 Routing table Idx index number of the list number IP IP address of GPRS network node number ID Modbus ID number 0 255 of slave device connected to GPRS network node with given IP address Comments entering Modbus ID of one of the Slave dev...

Страница 53: ...e s internal resources will be sent to appointed IP address Sending replies to any number of Master devices is possible Multimaster mode 8 2 5 4 Modbus RTU Mirror mode Modbus RTU Mirror is an extension of Modbus RTU Slave mode The behavior of the module is identical to Modbus RTU Slave mode seen from the GPRS point of view Remote access to internal module resources and to Slave devices connected t...

Страница 54: ...3 1 Modbus ID of Slave device Function Defines Modbus ID of Slave device from which configured data block is to be read Data type number Range 0 255 Default value 0 Comments setting Modbus ID to 0 zero switches the mapping off 8 2 5 4 3 2 Space Function selects Modbus space mapped from peripheral Slave device attached to PORT2 Data type selection list Range Bi In Binary inputs 1xxx read only Bi Ou...

Страница 55: ...its from mapped space are placed on consecutive bits in registers starting from least significant So in module in one registers 16 bits are stored Typical layout of mapped bit space Address of mapped space module 64 Address of mapped space SLAVE 3 Size of mapped space 20 8 2 5 4 3 6 Mapped space read interval Function Defines in seconds read interval of peripheral Slave device for update Data type...

Страница 56: ...s enables establishing a system consisting of several devices with functionality similar to point to point When a channel is established the module ignores packets received from other devices and all data received at PORT 2 are sent to the module with which the channel is established Transmission costs are thus reduced significantly Packets are sent to all recipients only at first transmission The...

Страница 57: ...updating It depends on speed of PORT2 along with size and number of defined mapped spaces 8 2 5 6 2 Number of retries Function defines number of attempts to transmit data via PORT2 in case of unconfirmed within time defined by transmission Timeout parameter reception Data type number Range 0 7 Default value 2 Comments value 0 zero forces max possible frequency of updating It depends on speed of PO...

Страница 58: ...t 8 2 5 6 6 Number of devices Function Defines number of declared register spaces devices read on PORT2 from peripheral devices operating on GazModem protocol Data type number Range 1 16 Default value 1 Comments n a 8 2 5 6 7 MC 1 16 The table defining consecutive data blocks read from peripheral devices attached to PORT2 operating in GazModem protocol The table can hold from 1 to 16 independent b...

Страница 59: ...em protocol Gazmodem 2 Read signals in Gaz Modem2 protocol Default value No Comments n a 8 2 5 6 7 4 Current data reading Function sets status of current data reading from gas meter Data type selection list Range Yes Current data reading active No Current data reading inactive Default value No Comments n a 8 2 5 6 7 5 Current data block index Function Defines address of first current data register...

Страница 60: ...Defines in seconds an interval between readings from peripheral device operating on GazModem protocol in order to update measurement data Data type number Range 0 255 min Default value 5 min Comments value 0 zero forces max possible frequency of updating It depends on speed of PORT2 along with size and number of defined mapped spaces 8 2 5 7 2 Number of retries Function defines number of attempts ...

Страница 61: ...l for update measurement data The connection is via PORT 1 Data type number Range 0 65535 s Default value 180 s Comments value 0 zero forces max possible frequency of updating It depends on speed of PORT2 along with size and number of defined mapped spaces 8 2 5 7 7 Number of transmission retries to gas meter Function defines number of attempts to transmit data via PORT1 in case of unconfirmed wit...

Страница 62: ...an hold from 1 to 16 independent blocks in one or more devices 8 2 5 7 10 1 Address 1 16 Function Defines address of heat meter whose internal parameters shall be read Data type number Range 0 255 Default value 0 Comments address 255 means querying stopped 8 2 5 7 10 2 Geographical coordinates format Function Defines format of geographical coordinates received in NMEA 0183 protocol when writing in...

Страница 63: ... of parameters read from NMEA frames received at PORT2 When exceeded due to incomplete reception relevant bits signal that values in registers are out of date In other words older than the time declared in configuration Data type number Range 1 300 Default value 2 Comments n a 8 2 5 9 FlexSerial In FlexSerial mode MT 101 module can service units connected to PORT2 that employ non standard protocol...

Страница 64: ...01 has eight identical Binary inputs Inputs can operate in one of three functional modes Standard binary input counter input analogue input with conversion of frequency to analogue value Each mode has a set of specific configuration parameters 8 2 6 2 1 1 Name Function Enables entering a friendly input name e g connected to the function performed The name is displayed on list of terminals Data typ...

Страница 65: ...in reality one pulse 8 2 6 2 1 2 2 Analogue inputs Function Defines time of measuring frequency of input signal in order to convert it to analogue value Data type number Range 0 255 x 0 1 s Default value 0 Comments for 0 zero value filtering is off Setting high time value influences stabilizing of result after signal value change but allows better precision of measuring noisy signal 8 2 6 2 1 2 2 ...

Страница 66: ...mments high reference point for internal units 8 2 6 2 1 2 2 5 High reference engineering units Function used along with other reference parameters for rescaling input signal range to engineering units range Data type number Range 1 65535 Default value 2000 Comments high reference point for engineering units 8 2 6 2 1 2 2 6 Alarm HiHi Function Defines HiHi alarm level in engineering units for anal...

Страница 67: ...eering units Comments Sets An Lo flag used for rules processing The reset level for this flag depends on Alarm hysteresis value 8 2 6 2 1 2 2 10 Alarm hysteresis Function Defines hysteresis for analogue input alarm thresholds The value is in engineering units Data type number Range 1 65535 engineering units Default value 10 engineering units Comments setting proper hysteresis value for variable si...

Страница 68: ... counting direction bit Default value 0 Comments when counting up the counter is zeroed by next appearing pulse upon reaching declared value When counting down next pulse writes declared value into the counter upon reaching 0 0 zero value switches counting off 8 2 6 2 1 2 3 3 Activating slope Function selects counting direction Data type selection list Range Raising The change of counter state occ...

Страница 69: ...dly names facilitates recognition of destination and appropriate settings 8 2 6 2 2 2 Operating modes Function defines operating mode for outputs Q1 Q8 Data type selection list Range Binary input the input acts as typical binary input accepting positive and negative logic Analogue input the input acts as analogue input measuring frequency of incoming signal in range from 0 2 kHz Counter input the ...

Страница 70: ...g noisy signal 8 2 6 2 2 2 2 1 Engineering units Function Defines a name for engineering units Data type text Range letters and numerals max 16 characters Default value x Comments inserted text does not have any influence on the value of measured analogue signal 8 2 6 2 2 2 2 2 Low reference internal units Function used along with other reference parameters for rescaling input signal range to engi...

Страница 71: ...e input signal Data type number Range 0 65535 engineering units Default value 0 engineering units Comments Sets An HiHi flag used for rules processing The reset level for this flag depends on Alarm hysteresis value 8 2 6 2 2 2 2 7 Alarm Hi Function Defines Hi alarm level in engineering units for analogue input signal Data type number Range 0 65535 engineering units Default value 0 engineering unit...

Страница 72: ...rm flag when signal source is unstable 8 2 6 2 2 2 2 11 Dead band Function Defines size of dead band for values of analogue input in engineering units Data type number Range 0 65534 engineering units Default value 10 engineering units Comments Insensitivity band spans symmetrically with last recorded value in center Upon crossing this value the new value is recorded and insensitivity band is moved...

Страница 73: ...al change from 1 0 Default value Raising Comments n a 8 2 6 2 2 2 3 4 Filtering constant Function Defines in seconds value of min duration of altered state on input in order to consider state to be stable Data type number Range 0 00 163 83 s Default value 0 00 s Comments Setting value appropriate to contact characteristics eliminates disturbance caused by contact bounce thus preventing multiple re...

Страница 74: ... and numerals max 16 characters Default value x Comments inserted text does not have any influence on the value of measured analogue signal 8 2 6 2 3 4 Low reference internal units Function used along with other reference parameters for rescaling input signal range to engineering units range Data type number Range 0 65535 Default value 0 Comments low reference point for internal units 8 2 6 2 3 5 ...

Страница 75: ...g The reset level for this flag depends on Alarm hysteresis value 8 2 6 2 3 9 Alarm Hi Function Defines Hi alarm level in engineering units for analogue input signal Data type number Range 0 65535 engineering units Default value 0 engineering units Comments Sets An Hi flag used for rules processing The reset level for this flag depends on Alarm hysteresis value 8 2 6 2 3 9 1 Alarm Lo Function Defi...

Страница 76: ... insensitivity for analogue input signal changes in engineering units Data type number Range 0 65534 engineering units Default value 10 engineering units Comments the range of insensitivity stretches symmetrically around previously noted signal value Upon signal crosses range new signal value is noted so that it is in mid range and a An DB flag is set high in binary outputs space This flag can be ...

Страница 77: ...y Function defines control of transmitted byte Data type selection list Range n a None Even Odd List of available options Default value n a Comments For operating modes for ports with MODBUS protocol this setting has following influence on stop bits 1 stop bit for Even and Odd 2 stop bits for n a 8 2 6 4 Asynchronous clocks Two Asynchronous clocks can cyclically count time for up to days 8640000 s...

Страница 78: ...0 min Default value 0 min Comments 0 zero value switches the clock off 8 2 6 6 Logger This section s parameters define operation of internal Logger recording state changes on binary inputs outputs and analogue inputs state The capacity of internal buffer is 140 records New records are written into memory after changes of state on binary inputs outputs or at crossing of dead band for analogue input...

Страница 79: ...ced by setting MLOG_rd bit to 1 one in binary outputs space Note that when forcing some data may get lost if querying is too slow compared to object s dynamics If the buffer gets filled between readings new data will replace oldest data so the latest 140 records are preserved 8 2 6 6 4 Buffer flush interval Function Defines in seconds the interval of buffer flushing in automatic mode Data type num...

Страница 80: ...T Buffer active No MT2MT Buffer inactive Default value No Comments n a 8 2 6 7 2 Sending to PORT2 Function Defines whether received event data buffer has to be sent to PORT2 Data type selection list Range Yes Received data will be sent No Received data will not be sent Default value No Comments This parameter has no influence on events with status that are always sent to PORT2 8 2 6 7 3 Buffer add...

Страница 81: ...nts n a 8 2 6 8 2 Parameter 1 64 Consecutive parameters are defined as numbers ranging from 0 65535 8 2 7 Rules Rules group contains lists of transmission tasks performed by internal program when criteria defined in rules are met Tasks are divided into two groups rules concerning transmission of SMS messages rules concerning transmission of data In both cases the criteria are defined by using same...

Страница 82: ...ameters Trigger input Trigger flag SMS text Recipient number Status sending 8 2 7 1 2 1 Trigger input Function defines resource to observe Data type selection list Range n a the rule is inactive I1 I8 binary inputs Q1 Q8 binary outputs A1 A2 analogue inputs FS1_ups FS1_q FS1_gprs system trigger inputs P1 P32 user program inputs TMR1 TMR2 TMR3 TMR4 synchronous and asynchronous clocks trigger inputs...

Страница 83: ...rs If the length is greater the text will be truncated so that full status is sent 8 2 7 1 2 4 Recipient number Function selects message recipient number Data type selection list Range friendly names of recipients associated with phone numbers in Authorized numbers list Default value NUM 1 first number on the list Comments since recipient s phone number is selected from the list of friendly names ...

Страница 84: ...ue 8 2 7 2 1 Number of data sending rules Function declares number of SMS sending rules Data type number Range 1 32 Default value 1 Comments diminishing the number of rules does not delete settings until the configuration is written to the module 8 2 7 2 1 1 Data sending rule Each of rules residing on the list is defined by following parameters Trigger input Trigger flag IP Address Send Buffer add...

Страница 85: ...fault value n a Comments more about trigger inputs and flags in chapter Appendices 8 2 7 2 1 1 3 IP address Function selects recipient s IP address Data type selection list Range friendly names of recipients associated with IP addresses in Authorized numbers list Default value IP1 first number on the list Comments since recipient s IP address is selected from the list of friendly names it is impor...

Страница 86: ...upport the legacy firmware The term CLIP call describes attempts to establish a phone connection to a defined number This connection is not supposed to be picked up by the recipient Identification of sending module s phone number is enough to convey the alert The meaning of alert should be agreed upon Notice that recipient does not have to be a GSM network subscriber but must have a phone able to ...

Страница 87: ...settings until the configuration is written to the module 8 2 7 3 2 Number of trials Function defines number of consecutive retries if the called number is busy or unavailable Data type number Range 0 255 Default value 3 Comments 0 zero value results with no redial attempts 8 2 7 3 3 Interval between trials Function defines in seconds interval between consecutive redial attempts Data type number R...

Страница 88: ...igger inputs and flags in chapter Appendices 8 2 7 3 4 2 Trigger flag Function defines event triggering flag associated with selected trigger Data type selection list Range n a rule inactive Bi In 0 1 Bi In 1 0 Bi In Chg binary input state change Bi Out Err discrepancy between the forcing and output state Counter counter flip over up or down An LoLo An Lo An Hi An HiHi An Set Fall An Set Rise An D...

Страница 89: ... locally or remotely via GPRS For local configuration it is enough to secure a connection via RS232 cable Detailed description of local configuration is to be found in the MTM user manual For remote configuration it is vital that the computer running the configuration application has access to the APN where the configured module resides Detailed description of remote configuration is to be found i...

Страница 90: ...ically disrupted and restarted at the next 100ms round The program is capable of carrying approx 750 instructions in 100ms The function of copying the buffers copies approx 1500 registers in 100ms The function of fast copying of blocks copies approx 7000 registers in 100ms 9 2 Starting to work It is recommended to set up the working environment during the first run of the program For this purpose ...

Страница 91: ...e Contains PIN code of the SIM card placed in the modem employed to communicate with APN Modem port Contains number of the com port the GPRS modem is connected to RS 232 Port Contains number of the com port the programmed module is connected to via serial cable Select the chosen module and connection type In order to do so activate parameter Select from menu Module or click the icon on the toolbar...

Страница 92: ... the window contains a field with button groups dedicated to defining operations and constants On top there is a system menu and a toolbar with icons for frequently used functions At the bottom a status bar displays from the left status of command interpreter selected module s name and selected communication channel 9 3 1 Menu items 9 3 1 1 File ...

Страница 93: ... The icon on the toolbar performs same function Function File Stores the program from the table on the hard disc in clear text creating good documentation Function Exit Closes the application after confirmation The keyboard shortcut for this function is Ctrl X The icon on the toolbar performs same function 9 3 1 2 Module Module Menu consists of functions governing the state of programmed module Fu...

Страница 94: ...the green dot in lower left corner of the status bar Function Select Presents the list of defined modules for selection of the desired module The list has the option of selecting transmission mode via either RS232 cable or wireless GPRS connection using the module s IP address ...

Страница 95: ... the function Read program is active If the connection is not established or broken the control is gray and reading from the module is impossible In case of serial cable connection the queries about sequential program lines are sent Lines are continuously read and displayed in the table In GPRS mode there is a couple of seconds delay between the query and response arrival In order to speed the fun...

Страница 96: ...ponse displays status information in lower left corner of main window The menu item Help Transmission opens transmission window displaying sent commands and replies ON Line OFF Line differentiation is important during connection via modem in GPRS mode Leaving the application connected with the module for longer time results in higher costs of transmission since transfer may be roughly estimated to...

Страница 97: ...connection status The tool bar displays the icon closing the window The main window s tool bar icon toggles transmission window display Function Settings opens environment configuration window described in Starting to work section The icon on the toolbar performs same function Function About opens window displaying version number and Manufacturer s address data ...

Страница 98: ... 9 4 Program editor table The table has six columns Each column has specific role assigned to be performed by the command interpreter If defines the condition for the table row to be executed If not met the line will be skipped Execute expression defines the function to be performed Get X holds the first argument of interpreted function Get Y holds the second argument of interpreted function Store...

Страница 99: ...es Right column of numerical keyboard represent 4 standard arithmetical operations 9 6 Numeric keyboard Numerical keyboard has all keys active only when selected function allows arithmetic input If selected function allows only logical input only keys 0 and 1 meaning respectively False Never and True Always When selected function does not allow numerical input the keyboard is grayed out inactive ...

Страница 100: ...ard Detailed description of standard and auxiliary functions is located at chapter Description of program functions 9 8 Description of Program functions Boolean AND X Y get X bit get Y bit store result bit 0 0 0 0 1 0 1 0 0 1 1 1 Boolean OR X Y get X bit get Y bit store result bit 0 0 0 0 1 1 1 0 1 1 1 1 Boolean XOR X Y get X bit get Y bit store result bit 0 0 0 0 1 1 1 0 1 1 1 0 ...

Страница 101: ...get Y 0 Is X lower or equal Y get X register get Y register store result bit get X get Y 1 get X get Y 0 Is X equal Y get X register get Y register store result bit get X equal get Y 1 get X not equal get Y 0 Is X not equal Y get X register get Y register store result bit get X not equal get Y 1 get X equal get Y 0 Copy X value store result register get X register Copy Boolean X store result bit g...

Страница 102: ...ror which sets an error flag Examples 10 3 1 15 4 error 15 5 0 Negation store result register get X register CAUTION Note that all registers store unsigned values Only DREG registers can hold 32 bit signed values Using this function on DREG registers in will in most cases return an error Bitwise OR The function calculates logical sum of corresponding bits in 2 registers Example decimal hexadecimal...

Страница 103: ...een register space and bit addressed memory space Virtual registers from bit addressed memory spaces VREG_BIx binary inputs and VREG_BO binary outputs enable access from functions operating on registers to bit variables Virtual register mapping is sequential first register holds first 16 bits the next following 16 and so on For example Registe bit 0 bit 1 bit 2 bit 3 bit 4 bit 5 bit 6 bit 7 bit 8 ...

Страница 104: ...er 04F2 0001 1100 1111 0010 value get Y register 1820 0001 1000 1110 0010 mask store result bit 1 1 Buffer copy This function copies value of source buffer starting at register get X to destination buffer defined in store result The length of copied buffer depends on the value in get Y register The function stops when buffer length value is negative writing attempted beyond the buffer space copied...

Страница 105: ...m 0 store result get X get Y The function rises error flag when copied value exceeds the range of destination register or cell address lays beyond the space Example get X register XREG10 get Y register REG1 store result register DREG2 If REG1 4 than function performs the operation DREG2 XREG14 Write value to table The function writes numeric value to table starting with register store result The v...

Страница 106: ...r 10 store result register REG1 The result is REG1 340 Example 2 Table from DREG1 1 5 0 12000 23 340 1 25 340 5 65000 23 100000 65000 get X register DREG1 get Y register 12 store result register REG1 The result is REG1 65000 If register had the value of 13 for get Y the function would have returned REG1 value equal to 100000 Search for min value in table The function scans the table beginning with...

Страница 107: ...rt text to number The function converts decimal value from text to binary Get X defines start of the text buffer to convert Text characters are written to low order bytes of 16 bit registers Get Y defines max number of characters registers to convert The function after successful conversion writes the result in store result register The result is always an integer value If converted value had a de...

Страница 108: ...mber defines the number of digits after comma in resultant format tens number defines number of digits before comma 0 automatically 100 sets delimiter to instead of 200 forces adding a sign before positive value Furthermore the function writes the resultant number s length in characters to AUX_RET1 register If the converted number is larger then allowed range the function does not perform the conv...

Страница 109: ...ernal function blocks 9 9 1 Timers T1 T8 5 EN_Tx RST_Tx x 10ms 11 REG_Tx PV_Tx Tx X 0 1 2 5 8 3 4 6 7 CAUTION All variables in Modbus address space are updated after every cycle of internal program execution that is every 100ms ...

Страница 110: ...nverted value rising edge falling edge or change of state 9 11 Filling and modifying program table The program table has to be filled out with subsequent lines starting with the left column and moving towards the right column Double clicking on any given field in the table unfolds a list of variables or functions available to the given column In the Condition column double clicking unfolds a list ...

Страница 111: ...These will be either arithmetic or logical variables The same discrimination will be visible on the numerical keypad in the right side of the window In case of logical variables only the 0 and 1 buttons will be active Of course the names of variables or values can be entered from the computer keyboard If the function can only accept one argument it will be impossible to select and enter a second o...

Страница 112: ...ntrolling algorithm The device status LED which displays possible problems resulting from errors in processing of downloaded internal programs has to be verified 9 14 Examples of programs This chapter aims at acquainting the user with common methods of defining algorithms Programs included in this chapter are built on simple premises and do not take the fact that they are all made for purely educa...

Страница 113: ...switching on off is 1 second 9 14 4 2 pumps alternating action Next example illustrates alternating work of 2 pumps activated by respective Q1 and Q2 output When water level makes sensor on input I3 close start level the program turns resting output Qx on If the water level does not decrease and the sensor on I4 gets activated the resting pump is switched on and stays on until the level drops to u...

Страница 114: ...the condition is not met Operations on REG1 and M0 flag prepare tasks for the next sequence of pumping using Q1 and Q2 Altering functionality is based on checking the value of the first bit in REG1 The bit changes its value for each change of M0 marker 9 14 5 3 pumps toggle action In this example the levels of starting and stopping of 3 binary outputs are designed exactly as the previous example f...

Страница 115: ... is necessary to test values of receiving module s registers holding the status received last via GPRS from sending module MTProg recognizes it as RMT_IN input space RMT_ID_OUT sender s ID output space RMT_AN1 and RMT_AN2 input AN1 respectively AN2 Scheme Create the rule sending status triggered by any change of I1 addressed to remote module Download the program that checks RMT_IN and the value of...

Страница 116: ...e program generates cyclic transmission of SMS messages until I5 declared as alarm confirmation is activated or the alarm condition ceases I1 0 When binary input I1 is activated output Q1 is set high In MTManager the rule triggered by Q1 sending SMS is defined Simultaneous to I1 going high the timer 1 is activated and counts to PV_T1 amounting 600 6 seconds starts Upon reaching PV_T1 the flag T1 i...

Страница 117: ...and light source to Q1 When I1 is activated the module turns the light on for 10 seconds Repeated activation of I1 resets the time count back to 10 seconds 9 14 9 Logger program An example of creating 512 elements logger for AN1 with 1 sec interval activated when I1 1 ...

Страница 118: ...ing LED indicators placed on front panel of the MT 101 module are very convenient during start up procedure In order to understand their message please get acquainted with error codes Click on the LED area you want to get information about ...

Страница 119: ...dule much easier Flashing 2 Hz output LED signifies that there is a discrepancy between intended output state and its actual state This usually occurs when the load is missing or the circuit is shorted 10 1 2 Inputs I1 I8 LED indicators of Inputs I1 I8 signal high state of binary signal connected to I1 I8 inputs It takes place regardless of whether the module operates in positive or negative logic...

Страница 120: ... its duties Modules not logged in GSM GPRS network are not able to transmit data and performs cyclic resets and retries to log in 10 1 4 GSM activity LED indicators Tx and Rx of GSM activity signal respectively transmitting and receiving of data via GPRS Since SMS sending is a form of data transmission both data frame transmission and SMS transmission cause short flashes of Tx LED Short flashes of...

Страница 121: ...be replaced with one securing higher signal level Reading of signal level happens in the moment of login to network and every 12 minutes if the module operates in SMS mode Selection of GPRS mode only means that signal level is investigated only during login procedure typically at power up That does not pose any danger since no disturbances in module s operation mean that the signal strength is suf...

Страница 122: ... is inactive so Tx and Rx LED s show no activity 10 1 7 Module s status Module status group encompasses four LED indicators displaying the state of the circuit controlling the module s operation and with execution of user defined program Significance of LED indicators Err LED when lit the Err LED indicates an error forcing automatic reboot The reason may be lack of GPRS communication disabling tra...

Страница 123: ...re lit when value of analogue signal at corresponding input crosses the manually set alarm threshold 10 2 Unblocking of SIM card Three failed attempts of entering PIN code locks the SIM card and requires entering the PUK code In order to prevent this the module controls the number of failed attempts written into SIM card by allowing only two attempts making a third attempt impossible even if the t...

Страница 124: ...n a standard GSM mobile phone The phone will demand entering of PUK code at power up Entering correct PUK code unblocks the card and resets PIN fault counter making the card operational 10 3 Error signaling Despite the efforts of module designers and users errors in function do occur It is often imperative to diagnose and remove the cause of error Error signaling is a tool for solving problems LED...

Страница 125: ...is a lit ERR LED Error code numbers are displayed on signal level and GPRS LEDs When GPRS LED is off the module is automatically trying reinitiate transmission When GPRS LED is flashing user intervention is required Remove the reason for error and recycle the power ...

Страница 126: ... either a fault in program or a module defect If a critical error occurs please note the error code and contact the manufacturer 11 Technical data 11 1 General Dimensions height x width x length 105x86x60 mm Weight 300 g Mounting method DIN rail 35mm Operating temperature 200 550 C Protection class IP40 Max potential on any connector referenced to GND 60Vrms max Humidity 5 95 non condensing ...

Страница 127: ...S Class 10 Frequency range EGSM 900 MHz Transmitter from 880 MHz to 915 MHz Receiver from 925 MHz to 960 MHz Frequency range GSM 850 MHz Transmitter from 824 MHz to 849 MHz Receiver from 869 MHz to 894 MHz Peak transmitting power EGSM 900 MHz GSM 850 MHz 33 dBm 2W class 4 station Frequency range EGSM 1800 MHz Transmitter from 1710 MHz to 1785 MHz Receiver from 1805 MHz to 1880 MHz Frequency range ...

Страница 128: ...outputs Q1 Q8 Operating as binary output Recommended mean current for single output 50mA Single output current 350mA max Mean current for all outputs 400mA max Voltage drop for 350mA 3 5V max OFF state current 0 2mA max Operating as binary input counter Input voltage range 0 36V Input resistance 5 4 kΩ Input voltage ON 1 9V Input voltage OFF 0 3V max Frequency range in analogue mode 0 2kHz Min pul...

Страница 129: ...126 11 7 Drawings and dimensions ...

Страница 130: ...c equipment Thou most of modern electrical equipment is well RF Radio Frequency shielded there is no certainty that radio waves emitted by the telemetry module s antenna may have negative influence on its function 12 2 1 Heart pacemakers It is recommended that the distance between the antenna of telemetry module and the Heart Pacemaker is greater than 20 cm This distance is recommended by manufact...

Страница 131: ...a at his disposal besides voice communication These are SMS CSD and GPRS Since they offer different functionalities a short description is necessary 13 1 1 SMS Short Message Service the technology of sending text messages The length of the message is 160 characters Permitted characters are letters and numbers Despite of its popularity it is not an optimal service for telemetry The cost of an SMS i...

Страница 132: ...t connection with the network while paying only for the volume of transmitted data with no charge for maintaining the connection This makes establishing of on line services for minimal expenses possible An additional advantage is potentially high transmission speed up to 170kb s facilitating high data volume transmission GPRS standard supports four channel encoding schemes named respectively CS1 t...

Страница 133: ...n conditions 13 1 5 UMTS Universal Mobile Telecommunications System UMTS is a system of third generation cellular phone networks following 2G systems like GSM The new radio interface significantly improved data transfer between the subscriber and the network boosting the quality of service 384 kbit s throughput 13 1 6 HSDPA HSDPA High Speed Downlink Packet Access is a technology based on shared tr...

Страница 134: ...devices In this configuration one can access internal module resources discrete resources inputs outputs or access resources of a device connected to module s serial port or mixed access to all above mentioned 13 2 2 1 Using internal resources This configuration requires two MT 101 modules where one acts as a gateway to a transmission system PLC SCADA set in Modbus Master mode In this case the dev...

Страница 135: ...should be connected to PORT 2 of module B and query resources of address assigned to module Slave A The master can query module B provided that Modbus address of module B is sent along A system configured this way secures permanent access to all internal resources of the Slave including SMS services in situations defined during configuration If the master unit is a PC running on Windows the MT Dat...

Страница 136: ...for transmission of data in unknown protocol but increases costs of transmission since data is sent unselectively Reduction of transmission expenses is possible only by employing the function of transmission channel reservation 13 2 2 2 2 Configuration for GazModem mode The system consisting of MT 101 modules in GazModem mode integrates dispersed objects in gas metering systems equipped with elect...

Страница 137: ...mory In this setup MT 101 module may act as a concentrator for 16 devices Additionally in this mode connection of PORT1 to an auxiliary counter serving in Gaz Modem protocol is possible 13 2 2 2 4 Configuration for NMEA 0183 mode In NMEA 0183 mode MT 101 module monitors information delivered by weather stations like AIRMAR to PORT 2 which is stored in register memory space Beyond localization para...

Страница 138: ...t Ix x in range 1 8 Qx state of output Qx x in range 1 8 Anx analogue input x in range 1 2 space address access to internal variables I bits in binary inputs space Q bits in binary outputs space AI Input Registers 16 bit R Internal Registers 16 bit M Internal flags Not deleted and zeroed during module reset S Internal flags deleted and zeroed during module reset Examples of syntax that may along w...

Страница 139: ...t to originator Confirmation SMS starts with sign 13 4 Unlocking writing to internal registers Procedure when data writing protection is set to Yes When data overwriting protection option is set the module does not process frames trying to change internal resources Unblocking requires sending data along with password If received frame contents a valid password the module allows remote modification...

Страница 140: ...erial number of computer with public static IP 13 6 Data formats MT 101 module gives the user a choice of data frame format standard standard operating mode The units communicate directly with each other in the APN using static IP addresses allocated permanently to used SIM cards In this mode IP addresses of communicating modules are written into authorized units lists Open The same configuration ...

Страница 141: ...dule s Status format Status frame of MT 101 module is a sequence of four 16 bit registers from internal registers space read command 03H write 06H or 10H 0x03E4 Inputs space MT_IN I8 I1 IQ8 IQ1 0x03E5 Outputs space MT_OUT 0 0 Q8 Q1 0x03E6 AN1 input copy input Register 0x0004 MT_AN1 16 bit value 0x03E7 AN2 input copy of input Register 0x0005 MT_AN2 16 bit value A call upon this coherent area in mem...

Страница 142: ... to 1 Bi In 1 0 Binary inputs I1 I8 Q1 Q8 Flag assuming value True after change of binary input from 1 to 0 Bi In Chg Binary inputs I1 I8 Q1 Q8 Flag assuming value True after any change of binary input Bi Out Err Binary outputs Q1 Q8 Flag assuming value True if read outputs state does not comply with set state Counter Binary inputs I1 I8 Q1 Q8 Flag assuming value True when counter reaches set valu...

Страница 143: ...ront panel preserving relation to hysteresis AN Set Fall Analogue inputs A1 A2 Flag assuming value True if value if value of analogue input is lower than value set as threshold with SET button on front panel preserving relation to hysteresis 13 10 RM 120 Converter module RM 120 is used as an intermediate in communication between telemetry module and the heat meter employing M BUS transmission prot...

Страница 144: ...141 RXD RS232 sender input COM RS232 circuit ground RTS optional signaling for computers COM connection not used for MT module PE1 RS232 circuit ground ...

Страница 145: ... for analog input AN1 dead band cross over 0x0020 AN2_LoLo AN2_Lo AN2_Hi AN2_HiHi AN2_Set_F AN2_Set_R AN2_Dbd 0 Threshold bits for analog input AN2 dead band cross over VREG_BI2 0x0028 FS1_fs FS1_ovr FS1_ups FS1_q FS1_prog FS1_gprs FS1_event FS1_sms FS1_fs 1 first cycle of the program FS1_ovr 1 delayed cycle start previous cycle longer than 100ms FS1_ups 1 no supply on UPS pin FS1_q 1 no supply fo...

Страница 146: ... AI5_Lo AI5_Hi AI5_HiHi Threshold bits for frequency analog inputs AQ5 and AI5 VREG_BI7 0x0078 AQ6_LoLo AQ6_Lo AQ6_Hi AQ6_HiHi AI6_LoLo AI6_Lo AI6_Hi AI6_HiHi Threshold bits for frequency analog inputs AQ6 and AI6 0x0080 AQ7_LoLo AQ7_Lo AQ7_Hi AQ7_HiHi AI7_LoLo AI7_Lo AI7_Hi AI7_HiHi Threshold bits for frequency analog inputs AQ7 and AI7 VREG_BI8 0x0088 AQ8_LoLo AQ8_Lo AQ8_Hi AQ8_HiHi AI8_LoLo AI8...

Страница 147: ...T2MT_76 MT2MT_77 MT2MT_78 MT2MT_79 MT2MT_80 VREG_BI48 0x0308 MT2MT_81 MT2MT_82 MT2MT_83 MT2MT_84 MT2MT_85 MT2MT_86 MT2MT_87 MT2MT_88 0x0310 MT2MT_89 MT2MT_90 MT2MT_91 MT2MT_92 MT2MT_93 MT2MT_94 MT2MT_95 MT2MT_96 VREG_BI49 0x0318 MT2MT_97 MT2MT_98 MT2MT_99 MT2MT_10 0 MT2MT_101 MT2MT_102 MT2MT_10 3 MT2MT_10 4 0x0320 MT2MT_10 5 MT2MT_10 6 MT2MT_10 7 MT2MT_10 8 MT2MT_109 MT2MT_110 MT2MT_11 1 MT2MT_11 ...

Страница 148: ... MT2MT_22 7 MT2MT_22 8 MT2MT_229 MT2MT_230 MT2MT_23 1 MT2MT_23 2 0x03A0 MT2MT_23 3 MT2MT_23 4 MT2MT_23 5 MT2MT_23 6 MT2MT_237 MT2MT_238 MT2MT_23 9 MT2MT_24 0 VREG_BI58 0x03A8 MT2MT_24 1 MT2MT_24 2 MT2MT_24 3 MT2MT_24 4 MT2MT_245 MT2MT_246 MT2MT_24 7 MT2MT_24 8 0x03B0 MT2MT_24 9 MT2MT_25 0 MT2MT_25 1 MT2MT_25 2 MT2MT_253 MT2MT_254 MT2MT_25 5 MT2MT_25 6 VREG_BI59 0x03B8 FS2_apn 0 0 0 0 FS2_new FS2_s...

Страница 149: ...PS1_stop MLOG_act GPRS_data MLOG_rd P2RCV_err P2SND_err x x PS1_stop 1 Program stop MLOG_act 1 activate MiniLogger GPRS_data bit set at every reception of a data frame via GPRS MLOG_rd 1 force MiniLogger readout reset after readout P2RCV_err 1 byte reception error f e transmission parameter or buffer overflow reset by user program P2SND_err 1 buffer transmission error f e wrong size reset by user ...

Страница 150: ...Converter F U 0 2kHz Pin Q1 16 bit value 0x0012 Converter F U 0 2kHz Pin Q2 16 bit value 0x0013 Converter F U 0 2kHz Pin Q3 16 bit value 0x0014 Converter F U 0 2kHz Pin Q4 16 bit value 0x0015 Converter F U 0 2kHz Pin Q5 16 bit value 0x0016 Converter F U 0 2kHz Pin Q6 16 bit value 0x0017 Converter F U 0 2kHz Pin Q7 16 bit value 0x0018 Converter F U 0 2kHz Pin Q8 16 bit value 0x0019 Converter F U 0 ...

Страница 151: ...firmed frames high 16 bits 0x0077 low 16 bits 0x0078 GPRS statistics Reception Frames Type 0 high 16 bits 0x0079 low 16 bits 0x007A GPRS statistics Reception Frames Type 1 high 16 bits 0x007B low 16 bits 0x007C GPRS statistics Reception Rejected frames Type 0 module busy high 16 bits 0x007D low 16 bits 0x007E Number of attempts since power up informing on failed access attempts due to invalid pass...

Страница 152: ...ter input I3 Low 16 bits 0x0016 32 bit counter input I4 CNT_I4 High 16 bits 0x0017 32 bit counter input I4 Low 16 bits 0x0018 32 bit counter input I5 CNT_I5 High 16 bits 0x0019 32 bit counter input I5 Low 16 bits 0x001A 32 bit counter input I6 CNT_I6 High 16 bits 0x001B 32 bit counter input I6 Low 16 bits 0x001C 32 bit counter input I7 CNT_I7 High 16 bits 0x001D 32 bit counter input I7 Low 16 bits...

Страница 153: ... bit Program register unsigned value REG7 16 bit value 0x0047 16 bit Program register unsigned value REG8 16 bit value 0x0048 16 bit Program register unsigned value REG9 16 bit value 0x0049 16 bit Program register unsigned value REG10 16 bit value 0x004A 16 bit Program register unsigned value REG11 16 bit value 0x004B 16 bit Program register unsigned value REG12 16 bit value 0x004C 16 bit Program ...

Страница 154: ...er on input Q8 s Low 16 bits 0x0290 32 bit activity time counter on input I1 s CNT_ON_I1 High 16 bits 0x0291 32 bit activity time counter on input I1 s Low 16 bits 0x029E 32 bit activity time counter on input I8 s CNT_ON_I8 High 16 bits 0x029F 32 bit activity time counter on input I8 s Low 16 bits Mirror Device status Mirror HIGH byte LOW byte 0x03E4 Inputs space MT_IN I8 I1 IQ8 IQ1 0x03E5 Outputs...

Страница 155: ...s 00 59 16 bit value 0x2702 RTC hours 00 23 16 bit value 0x2703 RTC day of week 1 Saturday 7 Sunday 16 bit value 0x2704 RTC day of month 1 31 16 bit value 0x2705 RTC month 1 12 16 bit value 0x2706 RTC year 2000 2099 16 bit value 0x2707 RTC negated bits of RTC registers 1 protection against accidental RTC settings modification 16 bit value ...

Страница 156: ...258 30259 MC1VAR2_H 32 bit H L floating point 0x103 259 30260 MC1VAR2_L 0x104 260 30261 MC1VAR3_H 32 bit H L floating point 0x105 261 30262 MC1VAR3_L 0x10E 270 30271 MC1VAR8_H 32 bit H L floating point 0x10F 271 30272 MC1VAR8_L 0x110 272 30273 MC2VAR1_H 32 bit H L floating point 0x111 273 30274 MC2VAR1_L 0x11E 286 30287 MC2VAR8_H 32 bit H L floating point 0x11F 287 30288 MC2VAR8_L 0x1FE 510 30511 ...

Страница 157: ...c MODBUS 0x0B8 184 10185 MC1V1LL LL alarm bit for VAR1 counter 1 0x0B9 185 10186 MC1V1L L alarm bit for VAR1 counter 1 0x0BA 186 10187 MC1V1H H alarm bit for VAR1 counter 1 0x0BB 187 10188 MC1V1HH HH alarm bit for VAR1 counter 1 0x0BC 188 10189 MC1V2LL LL alarm bit for VAR2 counter 1 0x0BD 189 10190 MC1V2L L alarm bit for VAR2 counter 1 0x0BE 190 10191 MC1V2H H alarm bit for VAR2 counter 1 0x0BF 1...

Страница 158: ...C 4 200 512 30513 data read from counter LEC 5 240 576 30577 data read from counter LEC 6 280 640 30641 data read from counter LEC 7 2C0 704 30705 data read from counter LEC 8 300 768 30769 data read from counter LEC 9 340 832 30833 data read from counter LEC 10 380 896 30897 data read from counter LEC 11 3C0 960 30961 data read from counter LEC 12 400 1024 31025 data read from counter LEC 13 440 ...

Страница 159: ... 5 2 bytes R5 L H Signature 6 dword 32 bit H L LEC timestamp LEC timestamp 8 dword 32 bit H L LEC errorflag LEC error flags 10 word 16 bit seconds 0 59 MT101 timestamp 11 word 16 bit minutes 0 59 12 word 16 bit hours 0 23 13 word 16 bit day of week 1 7 14 word 16 bit day 1 31 15 word 16 bit month 1 12 16 word 16 bit year 2000 2099 17 word 16 bit high bits inform which fields were read in current f...

Страница 160: ... 41045 LEC1 lower threshold Energy J 416 1046 41047 LEC1 upper threshold Energy J 418 1048 41049 LEC1 lower threshold Working time h 41A 1050 41051 LEC1 upper threshold Working time h 41C 1052 41053 LEC1 Alarm hourly consumption for Aux water meter 1 m3 h 41E 1054 41055 LEC1 upper threshold Auxiliary water meter 1 m3 420 1056 41057 LEC1 Alarm hourly consumption for Aux water meter 2 m3 h 422 1058 ...

Страница 161: ...10181 proper communication with counter 13 SL13_ok 0B5 181 10182 proper communication with counter 14 SL14_ok 0B6 182 10183 proper communication with counter 15 SL15_ok 0B7 183 10184 proper communication with counter 16 SL16_ok alarm bits for heat consumption meters 0B8 184 10185 LEC1 lower threshold Supply temp C 0B9 185 10186 LEC1 upper threshold Supply temp C 0BA 186 10187 LEC1 lower threshold ...

Страница 162: ...1 7 Auxiliary resources of NMEA 0183 mode Binary outputs space information bits Address of bit Register address Description Validity register Address bit Hex dec MODB US 0x80 128 129 0x402 Latitude 0x401 0 0x81 129 130 0x404 Longitude 0x401 1 0x82 130 131 0x406 Altitude over sea level 0x401 2 0x83 131 132 0x408 Speed Over Ground 0x401 3 0x84 132 133 0x40A Course Over Ground 0x401 4 0x85 133 134 0x...

Страница 163: ...in tables point to placement of first register holding High order word of the number Low order word lays in next register Address 0x400 1024 Register of validity of NMEA variables Modbus 41025 This register is used to control whether values read from NMEA frames held in registers are valid up to date A High bit signals that data in corresponding register is valid while Low bit signals that registe...

Страница 164: ... FIX 1 Unit degrees True Frames GPRMC GPVTG Address 0x40C 1036 Number of satellites in use Modbus 41037 Format FIX 0 Frames GPGGA Address 0x40E 1038 Barometric pressure Modbus 41039 Format FIX 0 Unit hPa Frames WIMDA Address 0x410 1040 Air temperature Modbus 41041 Format FIX 1 Unit degrees Celsius C Frames WIMDA Address 0x412 1042 Relative humidity Modbus 41043 Format FIX 1 Unit Frames WIMDA Addre...

Страница 165: ...IX 1 Unit kilometers hour km h Frames WIMWV relative Address 0x41E 1054 Theoretical wind direction Modbus 41055 Format FIX 1 Unit degrees Frames WIMWV theoretical Address 0x420 1056 Theoretical wind speed Modbus 41057 Format FIX 1 Unit kilometers hour km h Frames WIMWV theoretical Address 0x422 1058 Relative wind chill temperature Modbus 41059 Format FIX 1 Unit degrees Frames WIXDR Address 0x424 1...