5.11.2 Contact type
This parameter lets choose the behavior that will have the binary input depending on if the contact is normally
open or normally closed.
o
There are two possible options to configure the contact type:
“NO: Normally Open”
and
“NC: Normally
Closed”
.
5.11.3 Debounce time
This parameter lets choose a debounce time (in milliseconds) that will be applied to the contact.
5.11.4 Disabling function
This parameter shows/hides the
Control_ Disable Input x
communication object which will let disable/enable the
input x.
o
If set to
“no”
any object will be shown.
o
When
“DPT 1.003: 0-Disable; 1-Enable”
is selected, the input can be disabled using the value
“0”
and
enabled using the value
“1”
.
o
When
“DPT 1.002: 1-True (Disable); 0-False (Enable)”
is selected, the input can be disabled using the
value
“1”
and enabled using the value
“0”
.
5.11.5 Function
This parameter lets choose the function that will have the binary input. There are 3 different functions available:
Occupancy (internal), On/Off and Window Contact (internal).
o
When
“Occupancy”
is selected, the binary input “x” will have the same behavior as configured in the
parameter “Occupanys” (section 5.10).
o
When
“On/Off
” is selected, the AC unit will turn off when the binary inpyt “x” is active.
o
When
“Window Contact (internal)”
is selected, the binary input “x” will have the same behavior as
configured in the parameter
“Window Contact” (section 5.9).