Temperature configuration dialog
All the parameters in this section are related with the Temperature properties and communication objects.
Figure 5.10
Tempeature settings
5.7.1 Set Point - Enable use of +/- obj for Setp Temp
This parameter shows/hides the
Control_ Setpoint Temp +/-
communication object which lets you change the
indoor unit setpoint temperature by using two different datapoint types.
o
If set to
“no”
the object will not be shown.
o
If set to
“yes”
the
Control_ Setpoint Temp +/-
object.
➢
DPT type for +/- Setp Temp object
This parameter lets choose between the datapoints
0-Up / 1-Down [DPT_1.008]
and
0-Decrease / 1-
Increase [DPT_1.007]
for the
Control_ Setpoint Temp +/-
object.
▪
Up / Increase
▪
Down / Decrease
…
16ºC
17ºC
32ºC
31ºC
(Upper limit)
(Lower limit)