25 / 48
When a value between
90%
and
100%
is sent to the
Control_
object, the fifth vane position will be selected.
The
Status_
object will return a
20%
for the first vane position, a
40%
for the second one, a
60%
for the
third one, an
80%
for the fourth one and a
100%
for the fifth and last one.
5.5.2 Enable use of bit-type Vane U-D objects (for Control)
This parameter shows/hides the bit-type
Control_ Vane Up-Down
objects.
o
If set to
“no”
the objects will not be shown.
o
If set to
“yes”
the
Control_ Vane Up-Down
objects for each Position (1 to 5) will appear. To activate a Vane
Position by using these objects, a
“1”
value has to be sent.
5.5.3 Enable use of bit-type Vane U-D objects (for Status)
This parameter shows/hides the bit-type
Status_ Vane Up-Down
objects.
o
If set to
“no”
the objects will not be shown.
o
If set to
“yes”
the
Status_ Vane Up-Down
objects for each Position (1 to N) will appear. When a Vane
Position is enabled, a
“1”
value is returned through its bit-type object.
Pos. 1
Pos. 3
100%
Status_
0%
90%
50%
Control_
object
Control_
Status_
30%
70%
Pos. 2
Control_
Status_
Pos. 4
Pos. 5
Control_
Control_
20%
40%
60%
80%
Status_
Status_