Reload last On/Off value when Occupied
If set to
“no”
, once the switch-off timeout has elapsed, any value will be reloaded.
If set to
“yes”
, once the switch-off timeout has elapsed, the last On/Off value will be reloaded.
•
If a
“1”
value is sent to
the
Control_ Occupancy
object after the timeout period, the indoor unit
will
turn on
.
•
If a
“0”
value is sent to
the
Control_ Occupancy
after the timeout period no action will be
performed.
➢
Lock ON when occupied
If set to
“no”
, On/Off commands while the room is occupied will be accepted.
•
If a
“1”
value is sent to the
Control_ Switch Off Timeout
object the switch-off timeout period will
begin again.
•
If a
“0”
value is sent to
the
Control_ Switch Off Timeout
object, no action will be performed.
If set to
“yes”
, On/Off commands, while the window is open, will be saved (but not applied). These
commands will be used in the next parameter if set to
“yes”
.
Binary Input “x” configuration dialogs
All the parameters in this section are related with the binary inputs properties and communication objects.
5.11.1 Enable use of
Input “x”
This parameter enables the use of the Input “x”.
o
If set to
“no”
the objects will not be shown.
o
If set to
“yes”
the
Status_ Inx
object(s) and new parameters will appear.