Intesis
Box
®
KNX
– IR Universal AC
User's manual r1.0 eng
© Intesis Software S.L.U. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SLU
URL
Email
tel
http://www.intesisbox.com
[email protected]
+34 938047134
19 / 48
Mode
All the parameters in this section are related with the different mode properties and communication objects.
The byte-type communication object for Mode works with the DTP_20.105. Auto mode will be enabled with a
“0”
value, Heat mode with a
“1”
value, Cool mode with a
“3”
value, Fan mode with a
“9”
value and Dry mode
with a
“14”
value.
Figure 5.6
AC mode additional communication objects
5.3.1 Enable use of bit-type Mode objects (for control)
This parameter shows/hides the bit-type
Control_ Mode
objects.
Figure 5.7
Communication object detail
o
If set to
“no”
the objects will not be shown.
o
If set to
“yes”
the
Control_ Mode
objects for Auto, Heat, Cool, Fan and Dry will appear. To activate a mode
by using these objects a
“1”
value has to be sent.
5.3.2 Enable use of bit-type Mode objects (for status)
This parameter shows/hides the bit-type
Status_ Mode
objects.
Figure 5.8
Communication object detail