Timeout to apply action (minutes)
This parameter lets you choose how much time to wait (in minutes) before executing the action specified
in the next parameter (
“Action after timeout elapsed”).
➢
Action
When
Switch Off AC
is selected, once the timeout has elapsed, the indoor unit will be turned off.
When
Apply Preset Delta
is selected, once the timeout has elapsed, a delta temperature will be applied
in order to save energy (decreasing the setpoint when in Heat mode, or increasing the setpoint when in
Cool mode). Also new parameters will appear.
➢
Temp delta decrease (HEAT) or increase (COOL) (ºC)
This parameter lets configure the delta temperature (increase or decrease) that will be applied
when the timeout has elapsed.
Important: When there is occupancy again after the application of a delta, the same delta will
be applied inversely. (i.e. In a room with AC in cool mode and 25ºC setpoint temperature, a
+2ºC delta is applied after the occupancy timeout, setting the setpoint at 27ºC because there
is no occupancy in the room. If the setpoint is raised to 29ºC during that period, when the room
is occupied again, a -2ºC delta will be applied and the final setpoint temperature will then be
27ºC).
➢
Second Action
If set to
“no”
nothing will be applied.
If set to
“yes”
, a new timeout will be enabled and two new parameters will appear.
➢
Timeout (2nd)
This parameter lets you choose how much time to wait (in minutes) before executing the action specified
in the next parameter (“Action after timeout elapsed”).
➢
Action (2nd)
When
Switch-Off
is selected, once the timeout has elapsed, the indoor unit will turn off.
When
Apply Preset Delta
is selected, once the timeout configured is extinguished, a delta temperature
will be applied (decreasing the setpoint when in Heat mode, or increasing the setpoint when in Cool
mode). Also new parameters will appear.
➢
Temp delta decrease (HEAT) or increase (COOL) (ºC)
This parameter lets configure the delta temperature that will be applied when the timeout is
extinguished.
Important: When there is occupancy again after the application of a delta, the same delta will
be applied inversely as explained above.