TruVision IP Thermal Camera Configuration Manual
51
For example, for “Alarm Rule” select
Min. Temperature is Lower than
, and set
the “Alarm Temperature” to 40 °C (104 F°). The device triggers an alarm when
the minimum temperature is lower than 40 °C.
d) Click
OK
to save the changes.
Frame rule:
Single frame
a) Click
to show the
Alarm Rule
setup window.
b) Set the alarm rule. Select one of the options from the drop-down list:
Max. temperature is higher than, Max. temperature is lower than, Min.
temperature is higher than, Min. temperature is lower than, Average temperature
is higher than, Average temperature is lower than, Temperature difference is
higher than, or Temperature difference is lower than.
c) Enter the temperature values of the
Alarm Pre-Alarm Temperature
,
Alarm
Temperature
, and
Tolerance Temperature
.
For example, select “Alarm Rule”
as T
emperature Difference is Higher than
,
and set the “Alarm Temperature”
to 10 °C (50 F°). The device triggers an alarm
when the difference between the minimum temperature and the maximum
temperature of the region is higher than 10 °C.
d) Click
OK
to save the changes.
- Or -
Two or more frames
When using two or more alarm frames, set the alarm for the region temperature
difference between two frames.
a) In the
Temperature Measurement and Alarm
widow, enable the frames alarm
rules that you want to include in the region temperature difference.
b) Click the
Region Temperature Difference Alarm
button to display the
“Region
Temperature Difference Alarm” window.