Intel® Server System M20MYP1UR System Integration and Service Guide
20
Figure 10. Processor clip sub-assembly to heat sink orientation
8.
Orient the processor clip sub-assembly over the processor heat sink so that all corner features are in
alignment.
Ensure Pin 1 indicators are aligned
as shown in the figure above.
Figure 11. Processor heat sink module (PHM)
9.
Push the processor clip sub-assembly down on to the processor heat sink until it snaps into place,
ensuring all four corners are secure. Processor clip sub assembly should sit flat on top of the heat sink.
2.3.2
Processor Installation
The Intel® Server System M20MYP1UR supports the installation of 1 or 2 processors. For the server to be
operational, at least one processor must be installed. When only one processor is installed, it must be
installed in the CPU 1 socket. The installation of a processor in the CPU 2 socket is optional. However, to
ensure proper airflow when the server system is operational, the CPU 2 heat sink must be installed at all
times.