3. Electrical Installation
- 62 -
3
Table 3-12 Models and dimensions of the JST crimp terminal above
Model
Dimensions (mm)
Crimping Tool
No.
d2 (Min.)
B (Max.)
L
F
E
D
d1
T
150-12
13.0
36.0
66.0
23.0
27.0
26.5
19.5
3.2
YPT-150-1
250-12
13.0
44.0
78.0
24.5
31.5
35.6
26.0
4.5
YF-1, YET-300-1
250-12
13.0
44.0
78.0
24.5
31.5
35.6
26.0
4.5
YF-1, YET-300-1
250-16
17.0
44.0
78.0
24.5
31.5
35.6
26.0
4.5
YF-1, YET-300-1
325-16
17.0
50.5
88.0
33.5
35.5
37.6
28.0
4.5
YF-1, YET-300-1
3.2.2 Main Circuit Cable Recommendations
Ƶ
Main Circuit Cable Selection
Inovance recommends symmetrical shielded cable as main circuit cable, which can
reduce electromagnetic radiation of entire conductive system compared with four-
conductor cable
Figure 3-15 Symmetrical shielded cable is recommended
PE
PE conductor
and shield
Shield
Shield
PE
PE
Shield