Appendix
- 287 -
12
Ƶ
Installing Fuse on the Input Side
To prevent accidents caused by short circuit, install fuse on the input side and the fuse
must comply with the UL standard.
6HOHFWWKHIXVHDFFRUGLQJWRWKHIROORZLQJ¿JXUH
Model
FWH Series Fuse
Manufacturer: Bussmann
Rated Current (A)
Model
MD290T18.5G/22P
80 FWH-80B
MD290T22G/30P
100 FWH-100B
MD290T30G/37P
100 FWH-100B
MD290T37G/45P
125 FWH-125B
MD290T45G/55P
150 FWH-150B
MD290T55G/75P
200 FWH-200B
MD290T75G/90P
250 FWH-250B
MD290T90G/110P
275 FWH-275B
MD290T110G/132P
325 FWH-325B
MD290T132G/160P
400 FWH-400B
MD290T160G/200P
500 FWH-500B
MD290T200G(-L)
MD290T220P(-L)
600
FWH-600B
MD290T250P(-L)
-
600
FWH-600B
MD290T220G(-L)
MD290T280P(-L)
700
FWH-700B
MD290T250G(-L)
MD290T315P(-L)
800
FWH-800B
MD290T280G(-L)
MD290T355P(-L)
800
FWH-800B
MD290T315G(-L)
MD290T400P(-L)
1000
170M5016
MD290T355G(-L)
MD290T450P(-L)
1000
170M5016
MD290T400G(-L)
MD290T500P(-L)
1400
170M6017
MD290T450G(-L)
-
1400
170M6017
Ƶ
Preventing Entry of Foreign Objects
7KHGULYHXQLWVPXVWEHLQVWDOOHGLQD¿UHSURRIFDELQHWZLWKGRRUVWKDWSURYLGHHIIHFWLYH
electrical and mechanical protection. The installation must conform to local and regional
laws and regulations, and to relevant IEC requirements.
Ƶ
Grounding
If using an AC drive of the 400 V class, tie the neutral point of the drive power supply to
ground.
Содержание MD290 Series
Страница 1: ......
Страница 79: ...3 Electrical Installation 78 3 ...
Страница 80: ...4 Operating Panel Keypad Display 4 1 Introduction 80 4 2 Inbuilt LED Operating Panel 80 ...
Страница 92: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 92 5 2 Setup Flowchart 93 ...
Страница 227: ...7 Interfaces and Communication 226 7 ...
Страница 285: ...10 Troubleshooting 284 11 ...
Страница 349: ......
Страница 350: ......