Appendix
- 318 -
12
Para. No. Para. Name
Setting Range
Default
Property
Page
F7-04
LED display running parameters 2
0000 to FFFF
7
6
5
4
3
2
1
0
PID feedback
PLC stage
Pulse reference (kHz)
Running frequency 2
Remaining running time
AI1 voltage before correction
AI2 voltage before correction
AI3 voltage before correction
15
14
12
11
10 9
8
Motor speed
Current power-on time (H)
Current running time (Min)
Pulse reference (Hz)
Communication reference
Encoder feedback speed (Hz)
Main frequency display (Hz)
Auxiliary frequency display (Hz)
13
0
ƿ
161
F7-05
LED display stop parameters
0000 to FFFF
7
6
5
4
3
2
1
0
Bus voltage (V)
DO state
AI1 voltage (V)
Count value
Frequency reference (Hz)
DI state
AI2 voltage (V)
AI3 voltage (V)
15
14
12
11
10 9
8
PLC stage
Pulse reference (kHz)
Length value
Reserved
13
Load speed
PID reference
Reserved
Reserved
33
ƿ
162
F7-06
Load speed display decimal
SRLQWFRHI¿FLHQW
0.001 to 65.000
1.000
ƿ
-
F7-07
Heatsink temperature of inverter
IGBT
-20°C to 120°C
-
Ɣ
-
F7-08
Product SN
-
-
Ɣ
-
F7-09
Accumulative running time
0 to 65535 h
-
Ɣ
-
F7-10
Performance software version
-
-
Ɣ
-
F7-11
Function software version
-
-
Ɣ
-
F7-12
Number of decimal places for
load speed display
10 to 23
1: 1 decimal place
2: 2 decimal places
Number of decimal places
of U0-14
0: 0 decimal place
1: 1 decimal place
2: 2 decimal places
3: 3 decimal places
Number of decimal
places of U0-19/U0-29
21
ƿ
-
F7-13
Accumulative power-on time
0 to 65535 h
-
Ɣ
-
F7-14
Accumulative power
consumption
0 to 65535 kWh
-
Ɣ
-
Содержание MD290 Series
Страница 1: ......
Страница 79: ...3 Electrical Installation 78 3 ...
Страница 80: ...4 Operating Panel Keypad Display 4 1 Introduction 80 4 2 Inbuilt LED Operating Panel 80 ...
Страница 92: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 92 5 2 Setup Flowchart 93 ...
Страница 227: ...7 Interfaces and Communication 226 7 ...
Страница 285: ...10 Troubleshooting 284 11 ...
Страница 349: ......
Страница 350: ......