6. Description of Parameters
- 157 -
6
6.6.5 Motor Overheat Protection
Function Code
Parameter Name
Setting Range
Default
F9-56
Type of motor temperature
sensor
0: No temperature sensor
1: PT100
2: PT1000
0
F9-57
Motor overheat protection
threshold
0°C to 200°C
110°C
F9-58
Motor overheat pre-warning
threshold
0°C to 200°C
90°C
A motor temperature sensor can be connected to AI3 and PGND on extension I/O card. This
input is used by the drive for motor overheat protection.
When input signal reaches the value set in F9-57, the AC drive detects Err25 and acts as
selected in thousands position in F9-48. When input signal reaches the value set in F9-58, digital
output terminal set for function 39 becomes on.
The drive supports both PT100 and PT1000. Make sure to set sensor type correctly. You can
view motor temperature in U0-34.
6.6.6 Power Dip Ride-through
The power dip ride-through function ensures the system to run continuously at occurrence of
momentary power loss.
When an instantaneous power loss occurs, the AC drive compensates DC bus voltage reduction
with real-time energy feedback by reducing output frequency, preventing the AC drive from
stopping due to undervoltage.
Ɣ
F9-59 = 1: It is applicable to large-inertia applications such as fan, water pump and centrifuge
Ɣ
F9-59 = 2: It is applicable to the textile industry.
Figure 6-44 Power dip ride-through
Time (t)
Bus
voltage
Output
frequency
F9-61
F9-60
F9-62
Power dip ride-through
Time (t)
Содержание MD290 Series
Страница 1: ......
Страница 79: ...3 Electrical Installation 78 3 ...
Страница 80: ...4 Operating Panel Keypad Display 4 1 Introduction 80 4 2 Inbuilt LED Operating Panel 80 ...
Страница 92: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 92 5 2 Setup Flowchart 93 ...
Страница 227: ...7 Interfaces and Communication 226 7 ...
Страница 285: ...10 Troubleshooting 284 11 ...
Страница 349: ......
Страница 350: ......