![Incon OPTImizer 2 Скачать руководство пользователя страница 68](http://html.mh-extra.com/html/incon/optimizer-2/optimizer-2_user-manual_2051173068.webp)
68
6.6.2 DNP3.0 Implementation Table
The following table identifies the variations, function codes, and qualifiers supported by the
OPTI
mizer
2
DNP Slave in both request messages and in response messages.
OBJECT
REQUEST
RESPONSE
Object
Number
Variation
Number
Description
Function
Code (Dec)
Qualifier Code
(Hex)
Function Code
(Dec)
Qualifier Code (Hex)
1
1
Binary Input - Single-
bit packed
1
(read)
06
(no range, or all)
129
(Response)
00, 01
(start-stop)
,
02
2
2
Binary Input Change
Event - with absolute
time
1
(read)
06
(no range, or all)
,
07, 08
(limited qty)
,
09
129
(Response)
17, 28
(index)
,
39
12
1
Pulsed Control -
control relay output
block
3
(select)
17, 28
(index)
,
39
129
(Response)
echo of request
12
1
Pulsed Control -
control relay output
block
4
(operate)
17, 28
(index)
,
39
129
(Response)
echo of request
12
1
Pulsed Control -
control relay output
block
5
(direct op.)
17, 28
(index)
,
39
129
(Response)
echo of request
20
1
Counter - 32-bit with
flag
1
(read)
06
(no range, or all)
129
(Response)
00, 01
(start-stop)
,
02
22
1
Counter Change
Event - 32-bit with flag
1
(read)
06
(no range, or all)
,
07, 08
(limited qty)
,
09
129
(Response)
17, 28
(index)
,
39
30
5
Analog Input - single-
precision, floating-
point with flag
1
(read)
06
(no range, or all)
129
(Response)
00, 01
(start-stop)
,
02
32
5
Analog Input Change
Event - single-
precision, floating-
point without time
1
(read)
06
(no range, or all)
,
07, 08
(limited qty)
,
09
129
(Response)
17, 28
(index)
,
39
41
1
Analog Output Block
- 32-bit
3
(select)
17, 28
(index)
,
39
129
(Response)
echo of request
41
1
Analog Output Block
- 32-bit
4
(operate)
17, 28
(index)
,
39
129
(Response)
echo of request
41
1
Analog Output Block
- 32-bit
5
(direct op.)
17, 28
(index)
,
39
129
(Response)
echo of request
41
2
Analog Output Block
- 16-bit
3
(select)
17, 28
(index)
,
39
129
(Response)
echo of request
41
2
Analog Output Block
- 16-bit
4
(operate)
17, 28
(index)
,
39
129
(Response)
echo of request
41
2
Analog Output Block
- 16-bit
5
(direct op.)
17, 28
(index)
,
39
129
(Response)
echo of request
41
3
Analog Output Block
- single-precision,
floating-point
3
(select)
17, 28
(index)
,
39
129
(Response)
echo of request
41
3
Analog Output Block
- single-precision,
floating-point
4
(operate)
17, 28
(index)
,
39
129
(Response)
echo of request