55
Alarm History Report
The Alarm History Report consists of: Code; Category; Device; Data; State; (Date & Time) Occurred and (Date & Time)
Cleared.
Code: The alarm Code is an abbreviation for the description of the alarm seen on the ALARM tab. The prefix “al” is used to
indicate that it is an Alarm code. The table below gives a description of each alarm Code:
Code:
Description:
Cause:
How to Clear:
alInvalidConfiguration
Invalid Setup
Configuration
The unit has not been
programmed
Enter configuration settings
alConfigurationDNP3
Invalid DNP3
Configuration
DNP3 settings are illegal
Reprogram DNP3 settings
alWarningLimit
Remaining Contact
Life Warning Limit
Contact Life has reached
the Warning Limit
On ACTION Tab: Preset Remaining
Contact Life below the Warning Limit
alDangerLimit
Remaining Contact
Life Danger Limit
Contact Life has reached
the Danger Limit
On ACTION Tab: Preset Remaining
Contact Life below the Danger Limit
alArcTimeLimit
Arc Time Limit
Excess Arc Time has
been detected
On ACTION Tab: Clear Latched Alarms
alRestrike
Restrike
A Restrike has been
detected
On ACTION Tab: Clear Latched Alarms
alClearingTimeLimit
Clearing Time Limit
Excess Clearing Time
has been detected
On ACTION Tab: Clear Latched Alarms
alTripTimeLimit
Trip Time Limit
Excess Trip Time has
been detected
On ACTION Tab: Clear Latched Alarms
alTravelTimeLimit
Travel Time Limit
Excess Travel Time has
been detected
On ACTION Tab: Clear Latched Alarms
alClosingTimeLimit
Closing Time Limit
Excess Closing Time has
been detected
On ACTION Tab: Clear Latched Alarms
alOperationCountLimit
Operation Count
Limit
Operation Count has
reached the Limit
On ACTION Tab: Reset Operations
Counter
alNoOperationsTimeLimit
No Operations Time
Limit
Time between CB
operations too long
Operate the circuit breaker
alABLogicAlarm
A-B Logic Alarm
Logic violation on A & B
inputs
Self-clears when the A-B Input logic is
OK
alConfigurationCbMonitor
Invalid CB Monitor
Config.
CB Monitor settings are
illegal
Reprogram CB Monitor settings
alLowGasYellowLimit
SF
6
Low Gas Yellow
Limit
Low SF
6
gas detected
Add gas to the CB
alLowGassRedLimit
SF
6
Low Gas Red
Limit
Very low SF
6
gas
detected
Add gas to the CB
alErraticSignal
Erratic Sensor
Signal
Erratic SF
6
Sensor
Signal detected
Self-clears when a signal is stable
alTrendLimit
SF
6
Trend Limit
SF
6
Trend Limit has been
reached
Stop loss of SF
6
; On ACTION Tab:
Reset SF
6
Trend Data
alNoSensorSignal
No Sensor Signal
Detected
No SF
6
sensor signal
Detected
Self-clears when a signal is detected
alSignalRangeError
SF
6
Sensor Signal
Range Error
SF
6
sensor signal out of
range
Self-clears when the signal is in range
alConfigurationSf6
Invalid SF
6
Configuration
SF
6
Monitor settings are
illegal
Reprogram SF
6
Monitor settings
alCTInputFailure
CT Input Failure
Bad CT Pickup Coil
Check wiring or replace CT Pickup Coil
alInternalError1
Internal Error #1
Data Overload
Contact Technical Support
alInputInvalid
Input Invalid
Software Malfunction
Contact Technical Support
alCBMonitorUnknownActifity CBM Unknown Activity Software Malfunction
Contact Technical Support
alSF6UnknownActivity
SF
6
Unknown
Activity
Software Malfunction
Contact Technical Support
alInternalErrorDNP3
Internal DNP3 Error
Software Malfunction
Contact Technical Support
Table 8: Alarm Codes