©HALE PRODUCTS, INC. Our policy is one of continuous development. We therefore
reserve the right to amend specifications without notice or obligation.
MAINTENANCE SCHEDULE FOR SMARTCAFS
NOTE
:
The HALE service intervals replace those in the Gardner Denver Compressor manuals.
EQUIPMENT
ACTION
Click below for Procedure W/ Internet
Hyperlinks or Internal Page Links
EVERY 3 MONTHS
DSD
Check the pump and gearbox oil levels
Do a vacuum test to test for leaks
Page
Compressor
Check the oil level and top up if necessary.
Run compressor for 15 minutes
Page
Check the drive belt tension and condition.
Page
Mixing Manifold
Grease air ratio control ball valve
Page
Foam unit 3.3/5.0/6.5
Check that foam pipe connections are tight
Foam unit Manual FSG-MNL-00158
Operate the system in bypass to move the
concentrate and prevent gelling (if concentrate is
left in the system
without use
for three months)
EVERY 12 MONTHS
Compressor
Change the air filter
Change the oil and oil filter
Hot Shift Clutch
Change the oil
Page
Gearbox
Change the gearbox oil
DSD Maintenance Manual 029-0020-93-0
Pump
Inspect the anode, replace if needed
DSD Maintenance Manual 029-0020-93-0
Priming pump
Clean & lubricate
Suction Manifold
Inspect the anodes, replace if needed
Page
Foam unit 3.3/5.0/6.5
Inspect wiring/connections, hoses/connections
Foam unit Manual FSG-MNL-00158
Clean the foam strainer
Verify water flow calibration
Verify foam feedback calibration
EVERY 24 MONTHS
Compressor
Replace the oil separator element
CAFS Maintenance & Repair Manual
EVERY 5 YEARS
Compressor
Replace the compressor drive belt
ATTENTION
In high usage or abnormal operating conditions, the above procedures may need to be more frequent.
The best practise is to flush the system after each use. Intervals are automatically tracked in the UV
Display under the maintenance tab.