6: M
OVE
I
NSTRUCTIONS
6-6
FT1A S
MART
A
XIS
U
SER
’
S
M
ANUAL
FT9Y-B1382
IMOV (Indirect Move)
Applicable CPU Modules
Valid Devices
For the valid device address range, see pages 6-1 and 6-2 (Basic Vol.).
Internal relays M0 through M1277 can be designated as D1. Special internal relays cannot be designated as D1.
When T (timer) or C (counter) is used as S1, S2, or D2, the device data is the timer/counter current value (TC or CC). When T (timer) or C (counter)
is used as D1, the device data is the timer/counter preset value (TP or CP) which can be 0 through 65535.
When F (float) data type is selected, only data register can be designated as S1 or D1.
When F (float) data type is selected and S1 does not comply with the normal floating-point format, a user program execution error will result,
turning on special internal relay M8004 and ERR LED on the CPU module.
Either source device S2 or destination device D2 does not have to be designated. If S2 or D2 is not designated, the source or destination device is
determined by S1 or D1 without offset.
Make sure that the source data determined by S1 + S2 and the destination data determined by D1 + D2 are within the valid device range. If the
derived source or destination device is out of the valid device range, a user program execution error will result, turning on special internal relay
M8004 and the ERR LED on the CPU module.
For user program execution errors, see Chapter 4 “User Program Execution Errors” on page 4-21.
Valid Data Types
S1 + S2
D1 + D2
When input is on, the values contained in devices designated by S1
and S2 are added to determine the source of data. The 16- or 32-bit
data so determined is moved to destination, which is determined by
the sum of values contained in devices designated by D1 and D2.
REP
**
S1(R)
*****
D1(R)
*****
IMOV(*)
S2
*****
D2
*****
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
Base address to move from
X
X
X
X
X
X
X
—
1-99
S2 (Source 2)
Offset for S1
X
X
X
X
X
X
X
—
—
D1 (Destination 1)
Base address to move to
—
X
X
X
X
X
—
1-99
D2 (Destination 2)
Offset for D1
X
X
X
X
X
X
X
—
—
W (word)
X
When a bit device such as I (input), Q (output), M (internal relay), or R (shift register) is designated as the source
or destination, 16 points (word data type) or 32 points (double-word data type) are used. When repeat is
designated for a bit device, the quantity of device bits increases in 16- or 32-point increments.
When a word device such as T (timer), C (counter), or D (data register) is designated as the source or
destination, 1 point (word data type) or 2 points (double-word or float data type) are used. When repeat is
designated for a word device, the quantity of device words increases in 1- or 2-point increments.
I (integer)
—
D (double word)
X
L (long)
—
F (float)
X
Содержание microsmart pentra
Страница 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Страница 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...