AND and ANDN (And Not)
The AND instruction is used for programming a NO contact in series. The ANDN instruction is used for programming a NC contact
in series. The AND or ANDN instruction is entered after the first set of contacts.
When both inputs I0 and I1 are on, output Q0 is on. When either input I0 or I1 is off, output Q0 is off.
When input I0 is on and input I1 is off, output Q1 is on. When either input I0 is off or input I1 is on, output Q1 is off.
Valid Devices
The valid device range depends on the CPU module type. For details, see pages 6-1 and 6-2.
Data registers can be used as bit devices with the data register number and the bit position separated by a period.
OR and ORN (Or Not)
The OR instruction is used for programming a NO contact in parallel. The ORN instruction is used for programming a NC contact in
parallel. The OR or ORN instruction is entered after the first set of contacts.
When either input I0 or I1 is on, output Q0 is on. When both inputs I0 and I1 are off, output Q0 is off.
When either input I0 is on or input I1 is off, output Q1 is on. When input I0 is off and input I1 is on, output Q1 is off.
Valid Devices
The valid device range depends on the CPU module type. For details, see pages 6-1 and 6-2.
Data registers can be used as bit devices with the data register number and the bit position separated by a period.
Ladder Diagram
I0
I1
I1
I0
I0
ON
OFF
I1
ON
OFF
Q0
ON
OFF
Q1
ON
OFF
Timing Chart
Q0
Q1
LOD
AND
OUT
LOD
ANDN
OUT
I0
I1
Q0
I0
I1
Q1
Program List
Instruction
Data
Instruction
I
Q
M
T
C
R
D
AND
ANDN
0-35
40-75
80-115
120-155
0-21
40-61
80-101
120-141
0-1277
8000-8177
0-199
0-199
0-127
0.0-1999.15
8000.0-8199.15
Ladder Diagram
I0
I0
I0
ON
OFF
I1
ON
OFF
Q0
ON
OFF
Q1
ON
OFF
Timing Chart
I1
I1
Q0
Q1
LOD
OR
OUT
LOD
ORN
OUT
I0
I1
Q0
I0
I1
Q1
Program List
Instruction
Data
Instruction
I
Q
M
T
C
R
D
OR
ORN
0-35
40-75
80-115
120-155
0-21
40-61
80-101
120-141
0-1277
8000-8177
0-199
0-199
0-127
0.0-1999.15
8000.0-8199.15
Содержание microsmart pentra
Страница 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Страница 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...