19: P
ULSE
O
UTPUT
I
NSTRUCTIONS
19-16
FT1A S
MART
A
XIS
U
SER
’
S
M
ANUAL
FT9Y-B1382
Settings
Device tab
1. Select instruction
This item selects the RAMP instruction to use from RAMP1 or RAMP2.
The reversible control mode that can be selected varies based on the instruction.
For limitations due to the combination of instruction, reversible control mode, and the pulse output mode, see "9. Reversible
control enable" on page 19-18.
2. S1 (source 1): Control register
S1 specifies the starting number of the data registers to use with the RAMP1 or RAMP2 instruction.
Starting from the specified number, 9 continuous words of data registers are used.
The range of available data register numbers is D0 to D991 and D1000 to D1991.
Note:
The upper and lower data registers change according to the 32-bit data storage method specified.
For details, see Chapter 5 "Special Functions" – "32-bit Data Storage Setting" in the FT1A Series Pro/Lite User's Manual.
1.
2.
3.
4.
Storage
destination
Function
Setting
Reference
Starting 0
Steady pulse frequency
Operation mode 0: 1 to 10,000
(increments of 1 Hz)
Operation mode 1: 20 to 10,000
(increments of 10 Hz)
"6. Steady pulse frequency" on page
19-18
Starting 1
Initial pulse frequency
Operation mode 0: 1 to 10,000
(increments of 1 Hz)
Operation mode 1: 20 to 10,000
(increments of 10 Hz)
"7. Initial pulse frequency" on page
19-18
Starting 2
Frequency change time
10 to 10,000 ms
"8. Frequency change time" on page
19-18
Starting 3
Control direction
0: Forward
1: Reverse
"10. Control direction" on page 19-18
Starting 4
Preset value (high word) (Note)
1 to 100,000,000 pulses
"11. Preset value" on page 19-18
Starting 5
Preset value (low word) (Note)
Starting 6
Current value (high word) (Note)
1 to 100,000,000 pulses
"12. Current value" on page 19-19
Starting 7
Current value (low word) (Note)
Starting 8
Error status
0 to 9
Содержание microsmart pentra
Страница 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Страница 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...