3: D
EVICE
A
DDRESSES
3-12
FT1A S
MART
A
XIS
U
SER
’
S
M
ANUAL
FT9Y-B1382
D8027-D8028 Slave Number
The slave number is stored to D8027 and D8028 when the communication mode of port 2 and 3 is maintenance communication or
Modbus RTU slave.
The slave number can be specified with either a constant or a data register in the function area settings. When data register is
specified, the slave number can be changed by storing the slave number in D8027 and D8028.
D8027: Port 2 Slave Number
D8028: Port 3 Slave Number
For SmartAxis Pro/Lite maintenance communication, see Chapter 9 “Maintenance Communication” - “Maintenance Communication
via Serial Communication” in the FT1A Series Pro/Lite User's Manual. For Modbus RTU slaves, see Chapter 11 “Modbus
Communication” - “Modbus Communication via Serial Communication” in the FT1A Series Pro/Lite User's Manual. For SmartAxis
Touch maintenance communication and Modbus RTU slaves, see Chapter # “Project Settings” - “# Project Settings Dialog Box” -
“#.## System Settings” in the FT1A Series Touch User's Manual.
D8029 System Software Version
The PLC system software version number is stored to D8029. This value is indicated in the PLC status dialog box called from the
WindLDR menu bar. Select
Online
>
Monitor
>
Monitor
, then select
Online
>
Status
D8030 Communication Adapter Information
Information about the communication adapters installed on the port 2 and port 3 connectors is stored to D8030.
D8031 Optional Cartridge Information
Information about the optional cartridge installed on the CPU module is stored to D8031.
D8032-D8035, D8037, D8038 Interrupt Input Jump Destination Label No.
Jump destination label numbers for interrupt inputs are stored in these special data registers. To use interrupt inputs, store the
label number that corresponds to the special data register allocated to the interrupt input.
D8032=I0, D8033=I2, D8034=I3, D8035=I5, D8037=I6, D8038=I7
For details on SmartAxis Pro/Lite interrupt inputs, see Chapter 5 “Special Functions” – “Interrupt Inputs” in the FT1A Series Pro/
Lite User's Manual. For details on SmartAxis Touch interrupt inputs, see Chapter # “Project Settings” – “#.## Functions” –
“Interrupt Inputs” in the FT1A Series Touch User's Manual.
D8036 Timer Interrupt Jump Destination Label No.
The jump destination label number when the timer interrupt occurs is stored in D8036. To use the timer interrupt, store the
corresponding label number.
For details on the SmartAxis Pro/Lite timer interrupt, see Chapter 5 “Special Functions” – “Timer Interrupt” in the FT1A Series Pro/
Lite User's Manual. For details on the SmartAxis Touch timer interrupt, see Chapter # “Project Settings” – “#.## Functions” –
“Timer Interrupt” in the FT1A Series Touch User's Manual.
D8039 SD Memory Card Capacity
The capacity of the inserted SD or SDHC (maximum size 32 GB) memory card in megabytes is stored to D8039.
0:
RS232C communication adapter is installed
1:
RS485 communication adapter is installed or no communication adapter is installed
Bit
0 0
Port 3
1
7
8
15
Bit
0
Port 2
D8030
Bit
Bit
0:
No optional cartridge is installed
1:
Memory cartridge is installed
2:
SD memory card is installed
3:
Memory cartridge and SD memory card are installed
Bit
0 0
SD memory card
1
7
8
15
Bit
0
Memory cartridge
D8031
Bit Bit
Содержание microsmart pentra
Страница 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Страница 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...