FT1A S
MART
A
XIS
U
SER
’
S
M
ANUAL
FT9Y-B1382
19-35
19: P
ULSE
O
UTPUT
I
NSTRUCTIONS
3. S2 (source 2): Initialization input
S2 specifies the initialization input.
When the initialization input S2 is turned on, the initial values configured in the WindLDR ARAMP instruction dialog box, on the
Setting
tab, are stored in the control registers.
An external input (I0 to I35) (Note) or an internal relay (M0 to M1277) can be specified.
When the initialization input is on, the initial values are written to the data registers with each scan. To only initialize the values
one time, use the initialization input in combination with the SOTU (single output up) instruction or the SOTD (single output
down) instruction.
Note:
For the 40-I/O type, external inputs (I0 to I27) can be used.
4. S3 (source 3): Interrupt input
When the interrupt input changes from off to on, the pulse output process for the running step is aborted, and pulse output
restarts with the settings for the step configured by the interrupt number.
In the following example, the interrupt input turns on while step 2 is running. Pulse output processing for step 2 aborts and the
operation transitions to step 12.
An external input (I0 to I35) or internal relay (M0 to M1277) can be specified as the interrupt input.
Notes:
Do not use the same input or internal relay as the interrupt input signal for the ARAMP1 and ARAMP2 instructions.
To use the high-speed interrupt input signal, set the relevant input to
Normal Input
under
Special Input
on
Function Area Settings
. Do
not use the input as interrupt input, catch input, high-speed counter, or frequency measurement.
When using the high-speed interrupt input, ensure that no chatter noise occurs in the interrupt input.
Step 2 (6 words)
Storage destination
Function
Setting
Reference
Starting 8
Steady pulse frequency
Mode 0: 1 to 10,000 (increments of 1 Hz)
Mode 1: 20 to 10,000 (increments of 10 Hz)
"13. Steady pulse
frequency" on page 19-39
:
:
:
:
Starting 13
Next step number
1 to 18
"17. Next step number" on
page 19-39
:
Step N (6 words)
Starting 2+N x 6-6
Steady pulse frequency
Mode 0: 1 to 10,000 (increments of 1 Hz)
Mode 1: 20 to 10,000 (increments of 10 Hz)
"13. Steady pulse
frequency" on page 19-39
:
:
:
:
Starting 7+N x 6-6
Next step number
1 to 18
"17. Next step number" on
page 19-39
High-speed
I0, I2, I3, I5, I6, I7
An interrupt is used to read the interrupt input.
The interrupt input can be read without being affected by the user program scan.
Normal
I1, I4, I10 to I35
M0 to M1277
The information updated in the END processing is read as the interrupt input.
It is affected by the user program scan.
Step 1
Step 2
Step 3
Step 4
Steady pulse
frequency
Frequency
change time
Steady pulse
frequency
Steady pulse
frequency
Step 12
Steady pulse
frequency
Interrupt input ON
Содержание microsmart pentra
Страница 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Страница 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...