3: D
EVICE
A
DDRESSES
3-6
FT1A S
MART
A
XIS
U
SER
’
S
M
ANUAL
FT9Y-B1382
M8022 User Communication Receive Instruction Cancel Flag (Port 2)
When M8022 is turned on, all RXD2 instructions ready for receiving user communication through port 2 are disabled.
M8023 User Communication Receive Instruction Cancel Flag (Port 3)
When M8023 is turned on, all RXD3 instructions ready for receiving user communication through port 3 are disabled.
M8024 BMOV/WSFT Executing Flag
While the BMOV or WSFT is executed, M8024 turns on. When completed, M8024 turns off. If the CPU is powered down while
executing BMOV or WSFT, M8024 remains on when the CPU is powered up again.
M8025 Maintain Outputs While CPU Stopped
Outputs are normally turned off when the CPU is stopped. M8025 is used to maintain the output statuses when the CPU is
stopped. When the CPU is stopped with M8025 turned on, the output ON/OFF statuses are maintained. When the CPU restarts,
M8025 is turned off automatically.
M8026 SD Memory Card Status
When an SD memory card is inserted into the SmartAxis, M8026 turns on. When an SD memory card is not inserted, M8026 turns
off.
M8027 SD Memory Card Writing Flag
While logging data is written to the SD memory card, M8027 turns on. When writing logging data is finished, M8027 turns off.
M8030-M8061 Special Internal Relays for High-speed Counter
Special internal relays used for the high-speed counter.
For details on the Pro/Lite high-speed counter, see Chapter 5 “Special Functions” – “High-speed Counter” in the FT1A Series Pro/
Lite User's Manual. For details on the Touch high-speed counter, see Chapter # “Project Settings” – “#.## Functions” – “High-
speed Counter” in the FT1A Series Touch User's Manual.
M8070-M8075 Interrupt Input Status
Turns on when the corresponding user interrupt is allowed. When interrupt inputs are disabled, these internal relays are turned off.
M8070=Interrupt input I0 status, M8071=Interrupt input I2 status, M8072=Interrupt input I3 status
M8073=Interrupt input I5 status, M8074=Interrupt input I6 status, M8075=Interrupt input I7 status
M8076 SD Memory Card Access Stop Flag
Access to the SD memory card is stopped when M8076 is turned off to on.
M8080-M8085 Interrupt Input Edge (ON: Rising, OFF: Falling)
This flag indicates whether the interrupt input is triggered with a rising edge or falling edge.
M8090-M8095 Catch Input ON/OFF Status
When a rising or falling input edge is detected during a scan, the input statuses of catch inputs Group 1/I0 through Group 6/I7 at
the moment are set to M8090 through M8095, respectively, without regard to the scan status. Only one edge is detected in one
scan. For the catch input function, see page 5-32.
M8100-M8102 User Communication Receive Instruction Cancel Flag
When M8100, M8101, or M8102 is turned on, all ERXD instructions ready for receiving user communication through connection 1,
connection 2, or connection 3 are disabled, respectively.
M8110-M8112 Connection Status
When SmartAxis and a network device are connected via the maintenance communication server, user communication server/
client, or Modbus TCP server/client, the connection status turns on. When no network devices are connected, the connection
status turns off.
These relays are always off for the 12-I/O type (CPU modules without Ethernet port).
Содержание microsmart pentra
Страница 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Страница 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...