26: D
ATA
L
OG
I
NSTRUCTIONS
26-2
FT1A S
MART
A
XIS
U
SER
’
S
M
ANUAL
FT9Y-B1382
Notes:
The number of DLOG instructions that can be programmed in a user program is 48. However, make sure that the folder name specified by the
DLOG instruction is not duplicated with the folder names specified by the other DLOG instructions. When the folders are duplicated, log data
with a mixed format is output to the same CSV file.
The DLOG instruction cannot be used in an interrupt program.
While the input to DLOG instruction is on, log data is repeatedly output to the CSV file. When you want to output the log data only one time,
add a SOTU (single output up instruction) or SOTD (single output down instruction) to the input condition. For SOTU (single output up
instruction) or SOTD (single output down instruction), see "Basic Instructions" - "SOTU and SOTD (Single Output Up and Down)" on page 5-
27.
The data writing process to the SD memory card for the DLOG instruction takes several scans. Once a DLOG instruction is executed, the
process continues until writing the log data is complete, regardless of any change in the instruction input. While the log data is being written
to the SD memory card, the instruction is not executed, even when the inputs to DLOG instructions are turned on. To execute the DLOG
instruction again, confirm that the previous data writing process has finished, and then execute the instruction.
Applicable CPU Modules
Valid Devices
Note:
Specify the folder name by entering characters.
Internal relays M0 through M1277 can be designated as D1. Special internal relays cannot be designated as D1.
Settings
1. S1 (source 1): Folder name
Specify the folder name on the SD memory card to store the log data with a desired text up to 8 single-byte alphanumeric
characters.
Notes:
The following single-byte characters cannot be used in the folder names:
/ \
: * ? " < > | # { } % & ~
Consecutive periods cannot be used in folder names.
A period cannot be used at the start or the end of the folder name.
Single-byte spaces at the start or the end of the folder name are omitted.
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
—
—
X
X
—
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
Folder name (Note)
—
—
—
—
—
—
—
—
—
D1 (Destination 1)
Completion output
—
—
—
—
—
—
—
—
D2 (Destination 2)
Execution status
—
—
—
—
—
—
X
—
—
8.
7.
6.
5.
1.
4.
9.
10.
2.
3.
Содержание microsmart pentra
Страница 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Страница 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...