12. Current value
The number of pulses output from the pulse output port is stored in this data register.
The current value is updated when the RAMP instruction is executed at each scan.
13. Error status
If a configuration error occurs when the RAMP instruction input changes from off to on, M8004 (user program execution error)
is turned on and this register is set to the error code.
Notes 1:
The number of pulses in the frequency change region calculated by the initial pulse frequency, steady pulse frequency, and frequency
change time has exceeded the total number of output pulses. Adjust the settings by decreasing the steady or initial pulse frequency or by
shortening the frequency change time.
Notes 2:
Set the initial pulse frequency so that it is lower than the steady pulse frequency.
Error code
Description
0
Normal
—
2
Initial pulse frequency designation
error
The initial pulse frequency was not set between 1 and 10,000 in operation mode 0.
The initial pulse frequency was not set between 20 and 10,000 in operation mode 1.
3
Preset value designation error
The preset value was not set between 1 to 100,000,000.
4
Steady pulse frequency
designation error
The steady pulse frequency was not set between 1 and 10,000 in operation mode 0.
The steady pulse frequency was not set between 20 and 10,000 in operation mode 1.
5
Frequency change time
designation error
The frequency change time was not set between 10 and 10,000.
7
Control direction designation error
The control direction was not set to 0 or 1.
8
Exceeded pulse count error
The number of frequency change pulses exceed the total number of output pulses
(Note 1).
9
The initial pulse frequency was set to the same frequency as the steady pulse frequency or it was set to a value larger than
the steady pulse frequency (Note 2).
Содержание microsmart pentra
Страница 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Страница 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...