A-3. DL-303 DCON Command Sets
- 93 -
5 for dew point temperature in 0.01°C,
6 for dew point temperature in 0.01°F
@AADI reads
DO
response
!AA00O00
@AADO0V
sets DO, V-> 0: off, 1: on
@AAEATCN enables
AI
alarm of a channel,
N = 0 for CO,
1 for CO
2
,
2 for relative humidity,
3 for temperature in 0.01°C,
4 for temperature in 0.01°F,
5 for dew point temperature in 0.01°C,
6 for dew point temperature in 0.01°F
T->M: momentary alarm, L: latched alarm
@AAHI(data)CN sets high alarm limit of an AI channel,
N = 0 for CO in 1ppm,
1 for CO
2
in 1ppm,
2 for relative humidity in 0.01%,
3 for temperature in 0.01°C,
4 for temperature in 0.01°F,
5 for dew point temperature in 0.01°C,
6 for dew point temperature in 0.01°F
@AAHO
reads humidity offset
@AAHO(data)
sets humidity offset, data in format of -100.00 ~ +100.00
@AALO(data)CN sets low alarm limit of an AI channel,
N = 2 for relative humidity in 0.01%,
3 for temperature in 0.01°C,
4 for temperature in 0.01°F,
5 for dew point temperature in 0.01°C,
6 for dew point temperature in 0.01°F
@AARACN
reads AI alarm enabled/disabled status of a channel
response
!AAN, N->0: disabled, 1: momentary, 2: latched