DL-300 Data Logger User Manual Version 1.1.0 Aug. 2015
- 25 -
3.6 RS-485
Tap the RS-485 item in the Settings
menu to enter the sub-menu.
Address
: Sets the address for a module.
Default: 1
Range: 0 ~ 255
Protocol
: Sets the communication protocol.
- ModbusRTU (default)
- DCON
- DCONChkSum: uses DCON protocol and enables checksum
validation feature
Baud Rate
Default: 9600
Support Baud Rate: 1200/ 2400/ 4800/ 9600/ 19200/ 38400/ 57600/
115200 (unit: bps)
Parity
Default: N,8,1
Support format: N81, N82, E81, O81
Response Delay (ms)
: Sets the delay time between receiving the command
and sending the data.
Default: 0 ms
Range: 0 ~ 30 (unit: ms)
Save
: Saves the modification and returns to the Settings menu.
All the changes take effect immediately after saving changes.
Skip
: Returns to the Settings menu without saving any changes.