Q10: How to calibrate the touch screen?
A10:
1. Set the
pin 3. Touch Calib
in ON position
and others in OFF position on SW1.
2. Power on the DL-300 module
3. Touch the white boxes displayed in turn.
4. Touch one blue box, till the module senses the
touch input and sounds. Then touch the next box
one by one till the 5 five boxes are sensed.
1
3
2
Note
:
After the 5 boxes are sensed, the
screen turns to homescreen and
calibration is complete. Please note
to set pin
3. Touch Calib
in OFF
position and reboot the module.
If the calibration is failed and the
screen does not turn to
homescreen, re-power-cycle the
module and restart calibration
process.