C-2. DL-302 Modbus Address Mappings (Base 1)
- 112 -
00294 alarm.
channel 1: relative humidity
channel 2: temperature in 0.01°C,
channel 3:temperature in 0.01°F,
channel 4: dew point temperature in 0.01°C,
channel 5: dew point temperature in 0.01°F
00305 ~
00310
High alarm status of channel 0 to 5. Write 1 to clear high latched
alarm.
channel 0: CO
2
channel 1: relative humidity
channel 2: temperature in 0.01°C,
channel 3:temperature in 0.01°F,
channel 4: dew point temperature in 0.01°C,
channel 5: dew point temperature in 0.01°F
R/W
00321 ~
00326
Enable/disable alarm of channel 0 to 5; write 0 to disable alarm or
write 1 to enable alarm.
channel 0: CO
2
channel 1: relative humidity
channel 2: temperature in 0.01°C,
channel 3:temperature in 0.01°F,
channel 4: dew point temperature in 0.01°C,
channel 5: dew point temperature in 0.01°F
R/W
00337 ~
00342
Alarm mode, momentary or latched, of channel 0 to 5; write 0 to
enable momentary alarm mode or write 1 to enable latched alarm
mode.
channel 0: CO
2
channel 1: relative humidity
channel 2: temperature in 0.01°C,
channel 3:temperature in 0.01°F,
channel 4: dew point temperature in 0.01°C,
channel 5: dew point temperature in 0.01°F
R/W
00385 ~
00390
Write 1 to clear high latched analog input value of channel 0 to 5 W
00417 ~
00422
Write 1 to clear low latched analog input value of channel 0 to 5
W