DL-300 Data Logger User Manual Version 1.1.0 Aug. 2015
- 30 -
4.4 Network
The networks parameters are set on this page including DHCP enabled/disabled,
IP/Subnet Mask/Gateway addresses, the port number and the NetID for Modbus TCP
communication. Remember to click on the
Update Settings
button to update new
parameters.
Item
Description
Default
System
Timeout
(Network
Watchdog)
Sets the timeout for rebooting a DL-300 logger when it is
abnormal or failure to communicate.
Range: 30 ~ 65535 (unit: second)
0 = Disable
0
(Disable)
TCP Timeout
Sets the timeout for disconnecting a TCP connection
when a DL-300 does not receive data coming from the
Ethernet port.
Range: 5 ~ 65535 (unit: second)
0 = Disable
180