C-1. DL-301 Modbus Address Mappings (Base 1)
- 100 -
Appendix C: Modbus Address Table
C-1. DL-301 Modbus Address Mappings (Base 1)
Address Description
Attribute
30001 ~
30006
40001 ~
40006
Analog input value of channel 0 to 5.
channel 0: CO in 1ppm,
channel 1: relative humidity in 0.01%,
channel 2: temperature in 0.01°C,
channel 3:temperature in 0.01°F,
channel 4: dew point temperature in 0.01°C,
channel 5: dew point temperature in 0.01°F
R
40225 ~
40230
High alarm limit of channel 0 to 5,
channel 0: CO in 1ppm,
channel 1: relative humidity in 0.01%,
channel 2: temperature in 0.01°C,
channel 3:temperature in 0.01°F,
channel 4: dew point temperature in 0.01°C,
channel 5: dew point temperature in 0.01°F
R/W
40234 ~
40238
Low alarm limit of channel 1 to 5,
channel 1: relative humidity in 0.01%,
channel 2: temperature in 0.01°C,
channel 3:temperature in 0.01°F,
channel 4: dew point temperature in 0.01°C,
channel 5: dew point temperature in 0.01°F
R/W
40272 Modbus
NetID
Only for Modbus TCP protocol
R/W
30301
40301
Number of the digital input channels
Only for Modbus TCP protocol
R
30311
40311
Number of the digital output channels
Only for Modbus TCP protocol
R
30321
40321
Number of the analog input channels
Only for Modbus TCP protocol
R