A-2. DL-302 DCON Command Sets
- 87 -
@AADI read
DO
response
!AA00O00
@AADO0V
set DO, V-> 0: off, 1: on
@AAEATCN
Enable AI alarm of a channel,
N = 0 for CO
2
,
1 for relative humidity,
2 for temperature in 0.01°C,
3 for temperature in 0.01°F,
4 for dew point temperature in 0.01°C,
5 for dew point temperature in 0.01°F
T = M for momentary alarm, L for latched alarm
@AAHI(data)CN Set high alarm limit of an AI channel,
N = 0 for CO
2
in 1ppm,
1 for relative humidity in 0.01%,
2 for temperature in 0.01°C,
3 for temperature in 0.01°F,
4 for dew point temperature in 0.01°C,
5 for dew point temperature in 0.01°F
@AAHO
Read humidity offset
@AAHO(data)
Set humidity offset, data in format of -100.00 ~ +100.00
@AALO(data)CN Set low alarm limit of an AI channel,
N = 1 for relative humidity in 0.01%,
2 for temperature in 0.01°C,
3 for temperature in 0.01°F,
4 for dew point temperature in 0.01°C,
5 for dew point temperature in 0.01°F
@AARACN
Read AI alarm enabled/disabled status of a channel
response
!AAN, N->0: disabled, 1: momentary, 2: latched