A-3. DL-303 DCON Command Sets
- 90 -
A-3. DL-303 DCON Command Sets
Command
Description
$AAF
reads firmware version
$AAI
reads INIT status
response:
!AA0 -> INIT short to GND
!AA1 -> else
$AAM
reads module name
$AAP
read Modbus RTU/DCON protocol
response:
!AA0 -> DCON
!AA1 -> Modbus RTU
$AAPN
sets Modbus RTU/DCON protocol
N-> 0: DCON, 1: Modbus RTU
$AA2 reads
configuration
$AA5
reads reset status
!AA1 first after power on, !AA0 others
#AA
reads All Analog Inputs
response
>(CO in 1 ppm) (CO2 in 1 ppm) (relative humidity in
0.01%)(temperature in 0.01°C)(temperature in 0.01°F) (dew
point temperature in 0.01°C)(dew point temperature in
0.01°F)
#AAN
reads Channel Analog Input
N = 0 for CO in 1 ppm,
1 for CO2 in 1 ppm,
2 for relative humidity in 0.01%,
3 for temperature in 0.01°C,
4 for temperature in 0.01°F,
5 for dew point temperature in 0.01°C,
6 for dew point temperature in 0.01°F
%AANNTTCCFF sets configuration,
AA: current address,
NN: new address,
TT = 00,