![ICP DAS USA DL-301 Скачать руководство пользователя страница 95](http://html1.mh-extra.com/html/icp-das-usa/dl-301/dl-301_user-manual_3539049095.webp)
A-3. DL-303 DCON Command Sets
- 91 -
CC: new baud rate
Bits 5:0 : Baud rate, 0x03 ~ 0x0A
Code
0x03
0x04
0x05
0x06
Baud
1200 2400 4800 9600
Code
0x07
0x08
0x09
0x0A
Baud 19200 38400 57600 115200
Bits 7:6
00: no parity, 1 stop bit (N,8,1)
01: no parity, 2 stop bits (N,8,2)
10: even parity, 1 stop bit (E,8,1)
11: odd parity, 1 stop bit (O,8,1)
FF: data format
Bit 6
0: checksum disabled
1: checksum enabled
@AAABC
reads status of the automatic baseline correction
response
!AAN, N=0: disabled, 1: enabled
@AAABCN
sets the automatic baseline correction
N->0: disabled, 1: enabled
@AABA
reads beep on alarm time
response
!AAHH, HH in hex, 0: disabled, 1 ~ 250: beep on alarm time in
seconds, 251: beep on alarm continuously
@AABAHH
sets beep on alarm
HH in hex, 0: disabled, 1 ~ 250: beep on alarm time in seconds, 251:
beep on alarm continuously
@AABL
reads LCD back light
response
!AAHH, HH: 00 ~ FF in hex
@AABLHH
sets LCD back light, HH: 00 ~ FF in hex
@AACH
clears all high latched analog inputs to the current values