C-3. DL-303 Modbus Address Mappings (Base 1)
- 118 -
00291 ~
00295
Low alarm status of channel 2 to 6. Write 1 to clear low latched
alarm.
channel 2: relative humidity,
channel 3: temperature in 0.01°C,
channel 4:temperature in 0.01°F,
channel 5: dew point temperature in 0.01°C,
channel 6: dew point temperature in 0.01°F
R/W
00305 ~
00311
High alarm status of channel 0 to 6. Write 1 to clear high latched
alarm.
channel 0: CO,
channel 1: CO
2
,
channel 2: relative humidity,
channel 3: temperature in 0.01°C,
channel 4:temperature in 0.01°F,
channel 5: dew point temperature in 0.01°C,
channel 6: dew point temperature in 0.01°F
R/W
00321 ~
00327
Enable/disable alarm of channel 0 to 6, write 0 to disable alarm;
write 1 to enable alarm.
channel 0: CO,
channel 1: CO
2
,
channel 2: relative humidity,
channel 3: temperature in 0.01°C,
channel 4:temperature in 0.01°F,
channel 5: dew point temperature in 0.01°C,
channel 6: dew point temperature in 0.01°F
R/W
00337 ~
00343
Alarm type, momentary or latched, of channel 0 to 6, write 0 to
enable momentary alarm mode; write 1 to enable latched alarm
mode.
channel 0: CO,
channel 1: CO
2
,
channel 2: relative humidity,
channel 3: temperature in 0.01°C,
channel 4:temperature in 0.01°F,
channel 5: dew point temperature in 0.01°C,
channel 6: dew point temperature in 0.01°F
R/W
00385 ~
00391
Write 1 to clear high latched analog input value of channel 0 to 6
channel 0: CO,
W