C-3. DL-303 Modbus Address Mappings (Base 1)
- 115 -
Address Description
Attribute
40497
Beep on alarm,
0: disable,
1 to 250: beep on alarm time in seconds,
251: beep on alarm continuously
R/W
40498
Screen saver time in seconds, 0 to 65535, 0: disable
R/W
30513 ~
30519
40513 ~
40519
High latched analog input value of channel 0 to 6
channel 0: CO in 1ppm,
channel 1: CO
2
in 1ppm,
channel 2: relative humidity in 0.01%,
channel 3: temperature in 0.01°C,
channel 4:temperature in 0.01°F,
channel 5: dew point temperature in 0.01°C,
channel 6: dew point temperature in 0.01°F
R
30545 ~
30551
40545 ~
40551
Low latched analog input value of channel 0 to 6
channel 0: CO in 1ppm,
channel 1: CO
2
in 1ppm,
channel 2: relative humidity in 0.01%,
channel 3: temperature in 0.01°C,
channel 4:temperature in 0.01°F,
channel 5: dew point temperature in 0.01°C,
channel 6: dew point temperature in 0.01°F
R
30556
40556
Module reset status,
1: power-on,
2: watchdog,
3: software reset command
Only for Modbus TCP protocol
R
40558
Ethernet host watchdog timeout value, 5 to 65535, in second,
0 to disable.
Only for Modbus TCP protocol
R/W
30559
40559
Ethernet host watchdog timeout count.
Only for Modbus TCP protocol
R
30560
40560
Module name, 0x0303
Only for Modbus TCP protocol
R
40564
TCP disconnection timeout value, 5 to 65535, in second,
0 to disable.
Only for Modbus TCP protocol
R/W