A-2. DL-302 DCON Command Sets
- 85 -
CC: new baud rate
Bits 5:0 : Baud rate, 0x03 ~ 0x0A
Code
0x03
0x04
0x05
0x06
Baud 1200 2400 4800 9600
Code
0x07
0x08
0x09
0x0A
Baud 19200 38400 57600 115200
Bits 7:6
00: no parity, 1 stop bit (N,8,1)
01: no parity, 2 stop bits (N,8,2)
10: even parity, 1 stop bit (E,8,1)
11: odd parity, 1 stop bit (O,8,1)
FF: data format
Bit 6
0: checksum disabled
1: checksum enabled
@AAABC
Read status of the automatic baseline correction
response
!AAN, N=0: disabled, 1: enabled
@AAABCN
Set the automatic baseline correction
N->0: disabled, 1: enabled
@AABA
Read beep on alarm time
response
!AAHH, HH in hex, 0: disabled, 1 ~ 250: beep on alarm time
in seconds, 251: beep on alarm continuously
@AABAHH
Set beep on alarm, HH in hex,
0: disabled,
1 ~ 250: beep on alarm time in seconds,
251: beep on alarm continuously
@AABL
Read LCD back light
response
!AAHH, HH: 00 ~ FF in hex
@AABLHH
Set LCD back light, HH: 00 ~ FF in hex
@AACH
Clear all high latched analog inputs to the current values