DL-300 Data Logger User Manual Version 1.1.0 Aug. 2015
- 76 -
Saving a message or displaying a dynamic message
Modbus commad: Write Multiple Registers (10h)
Modbus address: 450302 (C47Dh, base 1)
Data format: 'IM' + Message Index + Message Message Settings
Byte
0
1
2
3
4
N-1
N
N+1
Delimiter
Index
Message
String
Message
Settings
Data
I
(0x49)
M
(0x4D)
0 ~ 20 T
u
0
M
(0x4D)
I
(0x49)
1. Delimiter characters: IM
2. Index
The message with the index in the range of 0 to 19 will be saved in the DL-300. If the
index is assigned to 20, the followed message with be directly displayed and will not
be saved.
3. Message String
A message can have a maximum of 6 lines and 14 half-width characters or 7
full-width characters maximum each line. “\r” (0x0D) is used to do a new line. If the
length of a message string is odd, an end character “0” must be added.
4. Message Settings
The Message Settings is optional; at least one zero character must be added
between the message string and message settings.
Byte
N
N+1
N+2
N+3
N+4
N+5
Delimiter
0 0 0
0
0
0
X
Y
Background Color
Data
M
(0x4D)
I
(0x49)
Y
:
Beep, 0: OFF,1: ON
X
: Exit button,
0: Hide,1: Display
Red
0~255
Green
0~255
Blue
0~255
Delimiter Characters
: MI
N+2
:
Sets whether to use beep prompt sound and exit button.
Background Color and Text Color
: the color is expressed as a 24-bit RGB triplet,
each component of which can vary from 0 to 255.
LSB
MSB