Suction Temperature Low Checklist
Improper Installation
• Refer to “Installation/Visual Inspection Checklist” on
page 112
Discharge Pressure
• Discharge temperature is too low, and is affecting
suction temperature, refer to “Freeze Cycle Discharge
Temperature Low Checklist” on page 116.
Improper Refrigerant Charge
• Undercharged
• Wrong type of refrigerant
Other
• Non-Icetro components in system
• Improper water supply over evaporator refer to
”Water System Checklist” on page 113.
• Loss of heat transfer from tubing on back side of
evaporator
• Restricted/plugged liquid line drier
• Restricted/plugged tubing in suction side of
refrigeration system
NOTE: Do not limit your diagnosis to only the items listed
in the checklists.