DIAGNOSING AN ICE MACHINE THAT WILL NOT RUN
n
Warning
High (line) voltage is applied to the control board
at all times. Removing the control board fuse or
moving the 'ICE/OFF/WASH' switch to 'OFF' will not
remove the power supplied to the control board.
1. Verify primary voltage is supplied to ice machine and
the fuse/circuit breaker is closed.
2. Verify control board fuse is okay.
NOTE: If any control board lights are on, the fuse is okay.
3. Verify the bin switch functions properly. A defective
bin switch can falsely indicate a full bin of ice.
4. Verify 'ICE/OFF/WASH' switch functions properly.