SELF-CONTAINED RECOVERY/EVACUATION
1. Place the 'ICE/OFF/WASH' switch in the 'OFF' position.
2. Install manifold gauge set, charging cylinder/scale,
and recovery unit or two-stage vacuum pump.
3. Open high and low side on manifold gauge set.
4. Perform recovery or evacuation:
A. Recovery: Operate the recovery unit as directed
by the manufacturer’s instructions.
B. Evacuation prior to recharging: Pull the system
down to 500 microns. Then, allow the pump to
run for an additional half hour. Turn off the pump
and perform a standing vacuum leak check.
NOTE: Check for leaks using an electronic leak detector
after charging the ice machine.
Follow the Charging Procedures below.
CHARGING PROCEDURES
Important
The charge is critical on all Icetro ice machines. Use
a scale or a charging cylinder to ensure the proper
charge is installed.
1. Be sure the 'ICE/OFF/WASH' switch is in the 'OFF'
position.
2. Close the vacuum pump valve and the low side
manifold gauge valve.
3. Open the high side manifold gauge valve.
4. Open the charging cylinder and add the proper
refrigerant charge (shown on nameplate) through the
discharge service valve.
5. Let the system “settle” for 2 to 3 minutes.
6. Set the 'ICE/OFF/WASH' switch to the 'ON' position.
1
3
8
Содержание IC-0170A
Страница 1: ...Undercounter Ice Machines Technician s Handbook Revision Date 1 24 22...
Страница 2: ......
Страница 14: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 17: ...16 How to Read a Serial Number Full Serial Number...
Страница 154: ...WU 0100 WIRING DIAGRAM Self Contained Air cooled 153...
Страница 155: ...IC 0170 IU 0170 IC 0220 IU 0220 WIRING DIAGRAM Self Contained Air cooled 154...
Страница 156: ...Printed Circuit Bards PCB WU 0100 PCB 155...
Страница 161: ...SPACE FOR TECHNICIAN S NOTES...
Страница 162: ...SPACE FOR TECHNICIAN S NOTES...
Страница 163: ...SPACE FOR TECHNICIAN S NOTES...
Страница 164: ...SPACE FOR TECHNICIAN S NOTES...
Страница 165: ......