Table 10. Sensor information, event description, and service action for the 5104-22C, 9006-12P,
9006-22C, or 9006-22P (continued)
Sensor name (Sensor ID)
Event description
Service action
• CPU1 Temp (0x0B)
• CPU2 Temp (0x0D)
• Transition to Critical from Less
Severe
• Transition to Non-recoverable
from Less Severe
• Transition to Critical from Non-
recoverable
Ensure that there are no air flow
obstructions at the front or at the
rear of the system. Ensure that
the fans are operating properly.
• Lower Non-critical – going low
• Lower Non-critical – going high
• Lower Critical - going low
• Lower Critical – going high
• Lower Non-recoverable – going
low
• Lower Non-recoverable – going
high
• Upper Non-critical – going low
• Upper Non-critical – going high
• Upper Critical - going low
• Upper Critical - going high
• Upper Non-recoverable – going
low
• Upper Non-recoverable – going
high
No service action is required.
28 Power Systems: Problem analysis, system parts, and locations for the 5104-22C, 9006-12P, 9006-22C, and
9006-22P
Содержание Power Systems Series
Страница 14: ...xiv Power Systems Problem analysis system parts and locations for the 5104 22C 9006 12P 9006 22C and 9006 22P...
Страница 88: ...74 Power Systems Problem analysis system parts and locations for the 5104 22C 9006 12P 9006 22C and 9006 22P...
Страница 101: ...Additional system parts Figure 14 Additional system parts Finding parts and locations 87...
Страница 115: ...Additional system parts Figure 23 Additional system parts Finding parts and locations 101...
Страница 122: ...108 Power Systems Problem analysis system parts and locations for the 5104 22C 9006 12P 9006 22C and 9006 22P...
Страница 133: ......
Страница 134: ...IBM...