Alert Category:
Critical - Temperature
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0524
SNMP Trap ID:
0
Automatically notify Support:
No
User response:
Complete the following steps until the problem is solved:
1.
Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
2.
Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3.
Make sure that the room temperature is within operating specifications.
4.
If there are no other thermal issues, replace the I/O expansion adapter.
80070301-2c04ffff
Sensor Mezz Exp 4 temp has transitioned to non-recoverable from a less severe state.
Explanation:
The temperature of the I/O expansion adapter in I/O expansion connector 4 has exceeded its specified
threshold. The compute node has attempted a soft shutdown.
May also be shown as 800703012c04ffff or 0x800703012c04ffff
Severity:
Error
Alert Category:
Critical - Temperature
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0524
SNMP Trap ID:
0
Automatically notify Support:
No
User response:
Complete the following steps until the problem is solved:
1.
Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
2.
Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3.
Make sure that the room temperature is within operating specifications.
4.
If there are no other thermal issues, replace the I/O expansion adapter.
80070301-2d01ffff
Sensor PCH Overtemp has transitioned to non-recoverable from a less severe state.
Explanation:
A temperature has exceeded its specified threshold. The compute node will attempt a soft shutdown.
May also be shown as 800703012d01ffff or 0x800703012d01ffff
Severity:
Error
Alert Category:
Critical - Temperature
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0524
SNMP Trap ID:
0
Automatically notify Support:
No
User response:
Complete the following steps until the problem is solved:
1.
Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
2.
Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3.
Make sure that the room temperature is within operating specifications.
80070301-2c04ffff • 80070301-2d01ffff
Chapter 6. Troubleshooting
121
Содержание Flex System x440 Compute Node
Страница 1: ...IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 2: ......
Страница 3: ...IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 34: ...22 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 50: ...38 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 68: ...56 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 498: ...486 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 570: ...558 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 578: ...566 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 583: ......
Страница 584: ... Part Number 81Y1144 Printed in USA 1P P N 81Y1144 ...