806f090c-200effff
[PhysicalMemoryElementName] on Subsystem [MemoryElementName] Throttled.
Explanation:
This message is for the use case when an implementation has detected Memory has been Throttled.
May also be shown as 806f090c200effff or 0x806f090c200effff
Severity:
Warning
Alert Category:
System - Other
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0142
SNMP Trap ID:
22
Automatically notify Support:
No
User response:
Complete the following steps:
1.
Check the CMM or FSM event log for any fan or cooling related issues.
2.
Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3.
Make sure that the room temperature is within operating specifications.
4.
Make sure that the DIMM baffles are in place.
5.
If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
806f090c-200fffff
[PhysicalMemoryElementName] on Subsystem [MemoryElementName] Throttled.
Explanation:
This message is for the use case when an implementation has detected Memory has been Throttled.
May also be shown as 806f090c200fffff or 0x806f090c200fffff
Severity:
Warning
Alert Category:
System - Other
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0142
SNMP Trap ID:
22
Automatically notify Support:
No
User response:
Complete the following steps:
1.
Check the CMM or FSM event log for any fan or cooling related issues.
2.
Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3.
Make sure that the room temperature is within operating specifications.
4.
Make sure that the DIMM baffles are in place.
5.
If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
806f090c-2010ffff
[PhysicalMemoryElementName] on Subsystem [MemoryElementName] Throttled.
Explanation:
This message is for the use case when an implementation has detected Memory has been Throttled.
May also be shown as 806f090c2010ffff or 0x806f090c2010ffff
Severity:
Warning
Alert Category:
System - Other
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0142
SNMP Trap ID:
22
Automatically notify Support:
No
806f090c-200effff • 806f090c-2010ffff
252
IBM Flex System x440 Compute Node Types 7917 and 2584: Installation and Service Guide
Содержание Flex System x440 Compute Node
Страница 1: ...IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 2: ......
Страница 3: ...IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 34: ...22 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 50: ...38 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 68: ...56 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 498: ...486 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 570: ...558 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 578: ...566 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 583: ......
Страница 584: ... Part Number 81Y1144 Printed in USA 1P P N 81Y1144 ...