2.
Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3.
Make sure that the room temperature is within operating specifications.
4.
Make sure that the DIMM baffles are in place.
5.
If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
806f0a0c-200fffff
An Over-Temperature Condition has been detected on the [PhysicalMemoryElementName] on
Subsystem [MemoryElementName].
Explanation:
This message is for the use case when an implementation has detected an Over Temperature Condition
for Memory that has been Detected.
May also be shown as 806f0a0c200fffff or 0x806f0a0c200fffff
Severity:
Error
Alert Category:
Critical - Temperature
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0146
SNMP Trap ID:
0
Automatically notify Support:
No
User response:
Complete the following steps:
1.
Check the CMM or FSM event log for any fan or cooling related issues.
2.
Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3.
Make sure that the room temperature is within operating specifications.
4.
Make sure that the DIMM baffles are in place.
5.
If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
806f0a0c-2010ffff
An Over-Temperature Condition has been detected on the [PhysicalMemoryElementName] on
Subsystem [MemoryElementName].
Explanation:
This message is for the use case when an implementation has detected an Over Temperature Condition
for Memory that has been Detected.
May also be shown as 806f0a0c2010ffff or 0x806f0a0c2010ffff
Severity:
Error
Alert Category:
Critical - Temperature
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0146
SNMP Trap ID:
0
Automatically notify Support:
No
User response:
Complete the following steps:
1.
Check the CMM or FSM event log for any fan or cooling related issues.
2.
Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3.
Make sure that the room temperature is within operating specifications.
4.
Make sure that the DIMM baffles are in place.
5.
If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
806f0a0c-200fffff • 806f0a0c-2010ffff
274
IBM Flex System x440 Compute Node Types 7917 and 2584: Installation and Service Guide
Содержание Flex System x440 Compute Node
Страница 1: ...IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 2: ......
Страница 3: ...IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 34: ...22 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 50: ...38 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 68: ...56 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 498: ...486 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 570: ...558 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 578: ...566 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Страница 583: ......
Страница 584: ... Part Number 81Y1144 Printed in USA 1P P N 81Y1144 ...