11
Technical data
11.1 Main data
Manufacturer
iba AG, Germany
Order no.
13.120000
Description
PROFINET bus monitor
PROFINET interfaces
Number
3 (2 x PROFINET devices for up to 2 PROFINET lines,
1 x sniffer)
PROFINET devices
2 x 2-port switches
Each with 2 x RJ45 socket 10/100 Mbit/s, autonegotiation
With the autonegotiation switched off, the port P2R of each
device works as uplink port
TAP interface (sniffer)
2-port switch, 2 x RJ45 socket, 10/100 Mbit/s
Functions
2 x PROFINET device, shared device (up to 4 controllers each),
RT, IRT (≥ 250 μs),
MRP and MRPD Client, NetLoad Class III,
S2 system redundancy
ibaNet interface
Number
1 (e. g. for the connection to ibaPDA)
Design
Fiber optic cable
ibaNet protocol
32Mbit Flex (bidirectional)
Up to 15 devices can be connected in a FO ring topology
Can be used for data, settings and service purposes (e.g.
updates)
max. 1024 analog signals (BYTE, INT, WORD, DINT, DWORD,
FLOAT, Big/Little Endian) + max. 1024 digital signals (BOOL)
max. 4060 bytes at a cycle time of 1.4 ms
Data transmission rate
32 Mbit/s
Sampling time
From 125 µs, freely adjustable
Connector type
2 ST connectors for RX and TX
The use of fiber optic cables of type 62.5 μm/125 μm is
recommended. For information on cable length, see chap. 11.4.
Transmitting interface (TX)
Output power 50/125 µm FO cable
-19,8 dBm to -12,8 dBm
62,5/125 µm FO cable
-16 dBm to -9 dBm
100/140 µm FO cable
-12,5 dBm to -5,5 dBm
200 µm FO cable
-8,5 dBm to -1,5 dBm
Temperature range -40 °F to 185 °F (-40 °C to 85 °C)
Light wavelength 850 nm
Receiving interface (RX)
Sensitivity
62,5/125 µm LWL-Faser:
-30 dBm
Temperature 77 °F (25 °C)
2
Data for other FO cable diameters not specified