![HygroMatik WL-ROL 160-1200 Series Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/hygromatik/wl-rol-160-1200-series/wl-rol-160-1200-series_manual_2192888035.webp)
Page 35
9.4 Special maintenance and
repairs
9.4.1 Membrane exchange
The membranes undergo a natural decline in
performance over time, specifically:
•
annual reduction in water produced of
7%
•
annual increase in outlet water conduc-
tivity of 10%
After a certain period of operation, in relation
to the characteristics and volume of water
treated, the membranes tend to become
blocked, with a decline in efficiency. This
decline in membrane efficiency may depend
on two main factors:
•
blockage due to precipitation of iron or
calcium sulphate and carbonate
•
biological blockage
•
infrequent replacement of the CBC
(carbon block fi lter)
Replacement becomes necessary when the
system shows variations in the following fun-
damental parameters (for the same initial
feed water temperature):
•
decrease in water produced to a level
that is insufficient for the application
connected downstream of the reverse
osmosis system.
•
excessive increase in the conductivity
of the water produced to a level that is
excessive for the application connected
downstream of the reverse osmosis
system.
Before replacing the membrane(s), check
the following:
•
The ROL unit is switched off
•
The inlet valve is closed, there is no
pressure on the water line.
The steps for membrane replacement are
described in detail in the
chapter mechani-
cal installation.
9.4.2 Replacing the metering pump
fuse
The fuse on the metering pump shows only
be replaced by specialist personnel. The
replacement procedure is as follows:
»
Loosen the 2 screws in the upper
part of thepart of the pump
»
Holding the pump, remove the 6
screws at the rear
»
Slide out the rear part of the pump
until it is completely detached from
the front part, so as to access the
circuit at the front of the pump.
»
Be careful with the spring on the
injection element shaft
»
Locate the fuse and replace it with
an identical one
»
Reposition the rear part of the pump
until it is completely coupled with the
front part
»
Tighten the 6 screws on the pump
»
Replace the pump in the unit and
tighten the two screws to the frame.
1 fuse 2 power supply
1
2
Содержание WL-ROL 160-1200 Series
Страница 1: ...FlexLine Reverse osmosis plants MANUAL WLROL EN E 8881184 WLROL ENj WL ROL 160 1200...
Страница 62: ...Page 62...
Страница 65: ...Page 65 13 Declaration of Conformity...
Страница 66: ...Page 66...
Страница 72: ...Page 72 This page intentionally left blank...
Страница 73: ...SPA Page 73 This page intentionally left blank...