3. Alarm
3.1 Acknowledge alarm
Immediately upon release of an alarm, the below display is shown with the number of actual alarms
and the reason for the record.
The controller returns to main menu view via the keys
F1
or
Escape
.
The alarm record is maintained and can be called anew via the main menu.
The failure LED lights red for the duration of an alarm record.
The alarm is acknowledged via the keys
F3
or
Enter
.
NOTE:
Any failure must be eliminated prior being acknowledged.
Example 1:
Alarm „brine lack“
That is caused if regeneration is released but no saturated brine is available or
if salt must be added to the brine tank
Salt must be refilled into brine tank
A brine formation time (ca. 2 to 3 hours) must be allowed to pass
The alarm is automatically acknowledged by the controller once saturated brine is available
as the float in the brine tank rises and thus, closes the input contact
The number of alarms is reduced to zero / the red LED extinguishes
LED red - ON