Hydro-Control VI Installation Guide HD0455 Rev 1.9.0
Symptom: Faulty output
Possible explanation Check
Required result
Action required on failure
Incorrect OPTO
module used for the
output
Voltage range for
the output module.
As a quick guide,
look at the colour of
the OPTO module
by looking though
the holes in the
back of the
controller.
OPTO module
colour:
Red: DC module,
typically up to 60v
DC
Black: AC module,
typically up to 110v
AC
Contact Hydronix for correct
OPTO module rating.
Wiring fault
When the OPTO
switches on the
OPTO LED should
light up. Check
wiring whilst the
OPTO is on.
See User Guide for
more details.
Force relay to switch on and
check wiring. Go to Menu >
I/O Setup and Status. Select
output and switch on.
Blown fuse
Remove rear cover
and check
continuity of the
fuse on the specific
OPTO module
using a meter.
Continuity check
ok, zero ohms.
Contact Hydronix for
replacement fuse.
Содержание Hydro-Control VI
Страница 4: ...4 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Страница 6: ...6 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Страница 8: ...8 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Страница 30: ...Electrical Installation Chapter 3 30 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Страница 54: ...Commissioning Chapter 4 54 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Страница 68: ...System Design Chapter 5 68 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Страница 88: ...Remote Support Chapter 7 88 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Страница 102: ...Document Cross Reference Appendix D 102 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...