Hydro-Control VI Installation Guide HD0455 Rev 1.9.0
37
Fine Valve On Time
Seconds
0.5
0 – 100 s
Fine Valve Off Time
Seconds
0.5
0 – 100 s
Use Fine Valve Only
None
No
Yes/No
Averaging Time
Seconds
10
0 – 100 s
Cycle Loops
None
1
1 – 100
Resolution
Kg/lb
1
0-200
Water Mode
controls how the water is measured into the mixer. If using a water meter to
measure the water dosed into the mixer, this should be set to ‘Metered’. If using a weight
measurement system then ‘Weighed’ water mode should be selected. ‘Timed’ water mode is
recommended for use when there are problems with the water measurement device. More
information on selecting water modes is available in Chapter 5.
Pulses Per Litre
sets the number of pulses that are received when dosing one litre of water
into the mixer in Metered Mode.
Water Meter Timeout
is the amount of time after opening the water valve that the system will
wait before alarming if it has not received a water meter pulse.
Fine Delivery
is the quantity of water at the end of the preset or calculated dose that is fed
using the fine valve only.
Fine Valve Inflight
is the quantity of water that continues to flow after the fine valve has been
closed.
Coarse Valve Inflight
is the quantity of water that continues to flow after the coarse valve has
been closed. This valve is used when the Pre-wet phase is run in preset mode.
Fine Valve On Time
is the amount of time it takes to turn on the fine valve. This should be
referenced from the valve manufacturer’s data sheet.
Fine Valve Off Time
is the amount of time it takes to turn off the fine valve. This should be
referenced from the valve manufacturer’s data sheet.
The valve on/off times are used to set the minimum pulse of the valve during AUTO Mode
addition, to prevent the valves from being damaged due to excessive use.
Use Fine Valve Only
sets the system to only dose water using the fine valve. In this mode it
will never activate the coarse valve.
Averaging Time
is the amount of time at the end of the dry and wet mix phases that the system
will use for taking an average value of the moisture reading.
Cycle Loops
is a setting that is used to repeat the wet mix addition and the wet mixing phases.
It is generally only useful for linearity testing, and so should be left set to 1.
Resolution
sets the resolution of the weigh scale value for systems set to use weighed water.
This value is not displayed unless the water mode is set to weighed water.
Содержание Hydro-Control VI
Страница 4: ...4 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Страница 6: ...6 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Страница 8: ...8 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Страница 30: ...Electrical Installation Chapter 3 30 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Страница 54: ...Commissioning Chapter 4 54 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Страница 68: ...System Design Chapter 5 68 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Страница 88: ...Remote Support Chapter 7 88 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Страница 102: ...Document Cross Reference Appendix D 102 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...