UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
8 Technical Specifications
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
195
Item
Specifications
IEC61000-4-4
Surge protection
EN/IEC62040-2
IEC61000-4-5
Power frequency magnetic field
IEC61000-4-8
Voltage sag and short time
interruption
IEC61000-4-11
Table 8-5
Mains Input Electrical Specifications
Item
Specifications
Input system
Three-phase, four-wire, and PE
Rated input
voltage
380 V AC, 400 V AC, or 415 V AC (line voltage)
Input voltage
80–280 V AC (phase voltage)
30°C < ambient temperature ≤ 40°C: The UPS supports full load
when the voltage is 198–280 V AC. The load bearing capacity is
derated to 35% when the voltage is 198–80 V AC.
0°C ≤ ambient temperature ≤ 30°C: The UPS supports full load
when the voltage is 187–280 V AC. The load bearing capacity is
derated to 35% when the voltage is 187–80 V AC.
Rated frequency 50 Hz or 60 Hz
Input frequency
40–70 Hz
Input PF
> 0.99 (full load)
> 0.98 (half load)
THDi
THDi < 3% (full linear load)
THDi < 5% (full non-linear load)
Table 8-6
Bypass Input Electrical Specifications
Item
Specifications
Input system
Three-phase, four-wire, and PE
Rated input
voltage
380 V AC, 400 V AC, or 415 V AC (line voltage)
Rated frequency 50 Hz or 60 Hz
Input frequency
range